Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
137
2 Parameters
2.2 List of parameters
Description: Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
powered up.
Dependency: Only effective if p1030.0 = 0.
Refer to: p1030
Description: Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the setpoint
must be interconnected via a connector input.
Dependency: Refer to: p1030, p1035, p1036, p1042
Note: The effectiveness of the internal ramp-function generator can be set in automatic mode.
Description: Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency: Refer to: p1041
Description: Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency: Refer to: p1044
Note: The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description: Sets the signal source for the setting value for the motorized potentiometer.
Dependency: Refer to: p1043
Note: The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
p1040[0...n] Motorized potentiometer starting value / Mop start value
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1041[0...n] BI: Motorized potentiometer manual/automatic / Mop manual/auto
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
- - 0
p1042[0...n] CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
- - 0
p1043[0...n] BI: Motorized potentiometer accept setting value / MotP acc set val
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
- - 0
p1044[0...n] CI: Motorized potentiometer setting value / Mop set val
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
- - 0