Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
179
2 Parameters
2.2 List of parameters
Description: Sets the monitoring time for the Vdc_max controller.
If the down ramp of the speed setpoint is held for longer than the time set in p1284, then fault F07404 is output.
Description: Sets the switch-in level for the Vdc-min controller (kinetic buffering).
The value is obtained as follows:
p1286[V] = p1285[%] * sqrt(2) * p0210
Warning: An excessively high value may adversely affect normal drive operation.
Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Note: The Vdc_min controller is not switched back off until the DC-link voltage rises above the threshold 1.05 * p1286 and
the controller output is zero.
Description: Sets the dynamic factor for the Vdc_min controller (kinetic buffering).
100% means that p1290, p1291, and p1292 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case, p1290, p1291,
and p1292 are weighted with the dynamic factor p1287.
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Note: The gain factor is proportional to the capacitance of the DC link.
The parameter is pre-set to a value that is optimally adapted to the capacitance of the power unit.
p1284[0...n] Vdc_max controller time threshold (U/f) / Vdc_max t_thresh
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 300.000 [s] 4.000 [s]
p1285[0...n] Vdc_min controller switch-in level (kinetic buffering) (U/f) / Vdc_min on_level
PM240
PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
65 [%] 150 [%] 76 [%]
r1286 Vdc_min controller switch-in level (kinetic buffering) (U/f) / Vdc_min on_level
PM240
PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
- [V] - [V] - [V]
p1287[0...n] Vdc_min controller dynamic factor (kinetic buffering) (U/f) / Vdc_min dyn_factor
PM240
PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
1 [%] 10000 [%] 100 [%]
p1290[0...n] Vdc controller proportional gain (U/f) / Vdc_ctrl Kp
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0.00 100.00 1.00