Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
29
2 Parameters
2.2 List of parameters
Re p0014 = 1:
With this setting, alarm A01066 followed by alarm A01067 can occur if parameters are continually changed via a
fieldbus system.
Parameter changes are entered in the volatile memory (RAM) and also in the non-volatile buffer memory.
In the following cases, the entries in the buffer memory are transferred into the ROM and then the buffer memory is
cleared:
- p0971 = 1
- power down/power up the Control Unit
- change from p0014 = 1 to 0
Re p0014 = 2:
The procedure to clear the entries in the buffer memory is initiated.
p0014 is automatically set to 0 after the entries have been cleared.
Description: Runs the corresponding macro files.
Dependency: Refer to: p1000, r8570
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: Macros available as standard are described in the technical documentation of the particular product.
Description: Runs the corresponding macro files.
Dependency: Refer to: p1000, r8570
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: Macros available as standard are described in the technical documentation of the particular product.
Description: Displays the firmware version of the Control Unit.
Dependency: Refer to: r0197, r0198
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
p0015 Macro drive unit / Macro drv unit
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: C, C(1) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 999999 12
p0015 Macro drive unit / Macro drv unit
CU230P-2_DP
CU230P-2_PN
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: C, C(1) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 999999 7
r0018 Control Unit firmware version / CU FW version
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4294967295 -