Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
82 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the sensor type for the motor temperature monitoring.
Value: 0: No sensor
1: PTC alarm & timer
2: KTY84
4: Bimetallic NC contact alarm & timer
Dependency: A thermal motor model is calculated corresponding to p0612.
Caution: Re p0601 = 2:
If the motor temperature sensor is not connected but another encoder, then the temperature adaptation of the motor
resistances must be switched out (p0620 = 0). Otherwise, in controlled-loop operation, torque errors will occur that
will mean that the motor will not be able to be stopped.
Note: Re p0601 = 1:
Tripping resistance = 1650 Ohm. Wire breakage and short-circuit monitoring.
Description: Sets the alarm threshold for monitoring the motor temperature for motor temperature model 2 or KTY.
After the alarm threshold is exceeded, alarm A07910 is output and a timer is started.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency: Refer to: p0612
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the threshold for monitoring the motor temperature for motor temperature model 1/2 or KTY.
Motor temperature model 1 (p0612.0 = 1): alarm threshold
- Alarm A07012 is output after the alarm threshold is exceeded.
Motor temperature model 2 (p0612.1 = 1) or KTY: fault threshold
- Fault F07011 is output after the fault threshold is exceeded.
Dependency: Refer to: p0611, p0612
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Motor temperature model 1:
p0605 also defines the target temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on the
time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current and
the reference value p0305.
p0601[0...n] Motor temperature sensor type / Mot_temp_sens type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 8016
Min Max Factory setting
0 4 0
p0604[0...n] Mot_temp_mod 2/KTY alarm threshold / Mod 2/KTY A thresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
0.0 [°C] 240.0 [°C] 130.0 [°C]
p0605[0...n] Mot_temp_mod 1/2 threshold / Mod 1/2 threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016, 8017
Min Max Factory setting
0.0 [°C] 240.0 [°C] 145.0 [°C]