Operating Instructions

List of parameters
Parameters
1-309
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 4 as a [%].
Dependency: Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3328, p3329
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency: Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency: Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: Sets the signal source for command 1 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3331, p3332, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
p3327[0...n] Fluid flow machine speed point 4 / Fluid_mach n4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 100.00 75.00
p3328[0...n] Fluid flow machine power point 5 / Fluid_mach P5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 100.00 100.00
p3329[0...n] Fluid flow machine speed point 5 / Fluid_mach n5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 100.00 100.00
p3330[0...n] BI: 2/3 wire control command 1 / 2/3 wire cmd 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0