Operating Instructions

List of parameters
Parameters
1-377
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the ramp-up time for the free technology controller 0.
Dependency: Refer to: p11058
Note: The ramp-up time is referred to 100 %.
Description: Sets the ramp-down time for the free technology controller 0.
Dependency: Refer to: p11057
Note: The ramp-down time is referred to 100 %.
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 0.
Description: Sets the signal source for the actual value of the free technology controller 0.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 0.
p11057 Free tec_ctrl 0 setpoint ramp-up time / Ftec0 setp t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
p11058 Free tec_ctrl 0 setpoint ramp-down time / Ftec0 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r11060 CO: Free tec_ctrl 0 setpoint after ramp-function generator / Ftec0 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_2 Unit selection: p11026 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11064 CI: Free tec_ctrl 0 actual value signal source / Ftec0 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11065 Free tec_ctrl 0 actual value smoothing time constant / Ftec0 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]