Operating Instructions

List of parameters
Parameters
1-145
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the signal source to invert the setpoint.
Dependency: Refer to: r1198
Caution: If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to invert the setpoint.
Dependency: Refer to: r1198
Caution: If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description: Displays the setpoint at the input of the ramp-function generator.
p1113[0...n] BI: Setpoint inversion / Setp inv
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2441, 2442, 2505,
3040
Min Max Factory setting
- - [0] 722.1
[1] 0
[2] 0
[3] 0
p1113[0...n] BI: Setpoint inversion / Setp inv
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2441, 2442, 2505,
3040
Min Max Factory setting
- - [0] 2090.11
[1] 0
[2] 0
[3] 0
r1114 CO: Setpoint after the direction limiting / Setp after limit
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1550, 3040, 3050
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1119 CO: Ramp-function generator setpoint at the input / RFG setp at inp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1550, 1690, 3050,
3060, 3070
Min Max Factory setting
- [rpm] - [rpm] - [rpm]