List of parameters
Parameters
1-213
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Dependency: Default setting PM260: 103 %.
Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
Description: Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
Note: A higher filter time constant can help to dampen (attenuate) low-frequency oscillations of the DC link voltage.
Description: Displays the effective modulator mode.
Value: 1: Flat top modulation (FLB)
2: Space vector modulation (SVM)
9: Optimized pulse pattern
p1803[0...n] Maximum modulation depth / Modulat depth max
PM330 Access level: 4 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
PM230
PM240
PM250, PM260
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
PM330 Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 6.0 [ms]
r1809 CO: Modulator mode actual / Modulator mode act
PM230
PM240
PM250, PM260
Access level: 4 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 9 -