Operating Instructions

Parameters
List of parameters
1-34
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Value: 0: No measurement
115: Measurement q leakage inductance (part 2)
120: Speed controller optimization (vibration test)
140: Calculate speed controller setting
150: Measurement moment of inertia
170: Measurement magnetizing current and saturation characteristic
195: Measurement q leakage inductance (part 1)
200: Rotating measurement selected
220: identification leakage inductance
230: Identification rotor time constant
240: Identification stator inductance
250: Identification stator inductance LQLD
270: Identification stator resistance
290: Identification valve lockout time
300: Stationary measurement selected
Note: Re r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
Description: Displays the effective Command Data Set (CDS).
Dependency: Refer to: p0810, p0811, r0836
Note: The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
Description: Displays the effective Drive Data Set (DDS).
Dependency: Refer to: p0820, p0821, r0837
Note: When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
Description: Display and connector output for status word 1.
r0050.0...1 CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS eff. bit 0 ON OFF -
01 CDS eff. bit 1 ON OFF -
r0051.0...1 CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS eff. bit 0 ON OFF -
01 DDS eff. bit 1 ON OFF -
r0052.0...15 CO/BO: Status word 1 / ZSW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Rdy for switch on Yes No -
01 Ready Yes No -