Setup menu
The setup menu is a fixed sequence of screens that allow the user to perform the standard
commissioning of the Inverter.
Once a parameter value has been modified, there is no possibility to cancel the standard
commissioning process. In this case, the standard commissioning process must be
completed. If no parameter value has been modified, then a short press of
returns to the
previous screen and a long press (more than 3 seconds) of
returns to the top of the
Monitor menu.
When a parameter value has been modified and the new value confirmed by pressing
,
then the next parameter in the standard commissioning sequence is automatically displayed.
Editing parameters
Parameters can be modified use two methods; scrolling through the parameter values or
using the single digit methods. See Parameters (Page 33).
NOTICE
Important information on the latest changes to the firmware
There has been some major changes to the way that the commissioning software has been
implemented and it is recommended that you read all the information given at the following
links to the Siemens Industry Online Support (SIOS) site:
SINAMICS G120 Firmware V4.7 SP3 - Modified commissioning behavior
Modified commissioning behavior
(https://support.industry.siemens.com/cs/ww/en/view/109480663)
Standard commissioning
The Standard commissioning process requires the input of data which is specific to the
motor to which the Inverter is connected. The data regarding the attached motor can be
gathered from the motor's rating plate. An example of a typical motor rating plate is shown in
the following figure: