Setting functions
8.7 Application-specific functions
Converter with CU230P-2 Control Units
224 Operating Instructions, 04/2014, FW V4.7, A5E34257946B AA
Note
If you use a temperature sensor as the input for the technology controller, you have to
modify the scaling of the analog input.
Scaling example for LG-Ni1000:
0° C (p0757) = 0% (p0758); 100° C (p0759) = 100% (p0760)
Scaling example for Pt1000:
0° C (p0757) = 0% (p0758); 80% C (p0759) = 100% (p0760)
Please refer to the parameter list for more details.