Operating Instructions

Table Of Contents
Setting functions
8.7 Application-specific functions
Converter with CU230P-2 Control Units
232 Operating Instructions, 04/2014, FW V4.7, A5E34257946B AA
8.7.16
Bypass
The bypass function switches the motor from inverter operation+ to line system operation.
The following options are possible:
Bypass function when activating via a control signal (p1267.0 = 1)
Bypass function depending on the speed (p1267.1 = 1)
The inverter controls two contactors via its digital outputs. The inverter analyses the
feedback signals from the contactors via its digital inputs. If using direct connection logic
(high level = ON), both contactors should be NO contacts.
Figure 8-33 Bypass circuit for control using the inverter
Note
Flying restart must be acti
vated for the bypass function (p1200 = 1 or 4).
Note
Bypass mode in the essential service mode
The special features for bypass mode in the essential service mode are described in Section
Essentia
l service mode (Page 225).