Technical data
12.2 Technical data, Power Modules
Converter with CU230P-2 Control Units
Operating Instructions, 04/2014, FW V4.7, A5E34257946B AA
323
Table 12- 15 PM230, IP55, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - with filter, Class A
Order No. - with filter Class B
6SL3223-…
6SL3223-…
…0DE23-0AA0
…0DE23-0BA0
LO base load power
LO base load input current
LO base load output current
3 kW
8.0 A
7.7 A
HO base load power
HO base load input current
HO base load output current
2.2 kW
6.1 A
5.9 A
Fuse according to IEC
Fuse according to UL
3NA3803
10 A, Class J
Power loss
0.12 kW
Required cooling air flow
7 l/s
Cross section of line and motor cables 1 … 2.5 mm
2
1814 AWG
Tightening torque for line and motor cables
0.5 Nm / 4.4 lbf in
Weight
4.3 kg
Table 12- 16 PM230, IP55, Frame Sizes B, 3 AC 380 V … 480 V
Order No. - with filter, Class A
Order No. - with filter Class B
6SL3223-…
6SL3223-…
…0DE24-0AA0
…0DE24-0BA0
…0DE25-5AA0
…0DE25-5BA0
…0DE27-5AA0
…0DE27-5BA0
LO base load power
LO base load input current
LO base load output current
4 kW
10.5 A
10.2 A
5.5 kW
13.6 A
13.2 A
7.5 kW
18.6 A
18 A
HO base load power
HO base load input current
HO base load output current
3 kW
8.0 A
7.7 A
4 kW
10.5 A
10.2 A
5.5 kW
13.6 A
13.2 A
Fuse according to IEC
Fuse according to UL
3NA3805
16 A, Class J
3NA3807
25 A, Class J
3NA3810
35 A, Class J
Power loss
0.14 kW
0.18 kW
0.24 kW
Required cooling air flow
9 l/s
9 l/s
9 l/s
Cross section of line and motor cables 2.56 mm
2
1410 AWG
4 … 6 mm
2
1210 AWG
4 … 6 mm
2
1210 AWG
Tightening torque for line and motor cables
0.5 Nm / 4.4 lbf in
0.5 Nm / 4.4 lbf in
0.5 Nm / 4.4 lbf in
Weight
6.3 kg
6.3 kg
6.3 kg