User Manual
21
Transmission
Transmission technology serial, asynchronous
Baud rate 1,200 bit/s
Device properties
Protection class EN 60529 (DIN VDE 0470-1)
and DIN EN 50102
Safety measures Basic insulation required according
to IEC 60928
EMC requirements EN 50081/VDE 0839-81 and
EN 50082/VDE 0839-82
Ballast standards Safety (EN 61347)
Functionality (EN 60929)
Line current harmonics (EN 61000-3-2)
Radio interference suppression from
9 kHz to 300 MHz (EN 55015:2006 +
A1:2007)/CDN measurement
Immunity (EN 61547)
Conditions for use
Ambient temperature
for reliable lamp ignition
From -20 °C (preheating of both
lamp filaments)
Permissible temperature
range for reliable lamp
operation
-20 °C to +75 °C
Cable lengths as a
function of cross section
DALI cable length for copper at 25 °C
2.5 mm²: max. 300 m
1.5 mm²: max. 300 m
1.0 mm²: max. 224 m
0.75 mm²: max. 168 m
0.5 mm²: max. 112 m
Loop resistance max. 10 Ohm
Extra-low-voltage lines 2 x 2 x 0.8 (diameter)
Bus systems