Mounting guidelines
Route cables so that they are out of people’s reach
Route cables at an adequate distance from hot
piping, lightning protection systems and telecom-
munication lines
In horizontal cable runs: lay the cable preferably
at 30 cm below the ceiling level, and at either
30 or 100 cm above the floor level
In vertical cable runs: lay the cable preferably at
15 cm to the side of the building carcass (shell)
edges or corners
Source: DIN 18015