Mounting guidelines for door/window contacts
Mount on the upper edge of the door or window to
reliably detect and signal the reading even when the
window is tilted open
Attach the door/window contact to the stationary door/
window frame and mount the magnet on the moving
door panel or window casement
Make sure that the mounting plate and magnet are
located in close vertical alignment – with a gap of at
least 3 mm, but no more than 10 mm
Alternative mounting option: Mount on the bottom
edge of the door or window; by doing so, the status is
not reported when the window is tilted open, but rather
only when fully opened
Mounting guidelines