Application examples
Switching off standby
with DALI
Luminaires with electronic ballasts usually need a
closed-circuit current, even when the lighting system is
turned off or is in standby mode. This energy consump-
tion adds up, but can be conserved using the KNX/DALI
gateway Twin plus: by automatically cutting off power
to the electronic ballasts. After the lighting is turned off
and as soon as all electronic ballasts in the defined area
are no longer needed for lighting, the ballasts can be
disconnected from the power supply via a command from
a switch actuator controlled for this purpose. If one or
more luminaires are in operation, the switch actuator first
restores power to the electronic ballast, and the gateway
dims the luminaire to the required brightness level.
Max. 64 2-mA
electronic
ballasts
per channel
DALI pushbutton
interface 4-fold
(max. 16 per
channel)
Max. 190 mA
per DALI Channel
DALI multisensor
(max. 8 PIR per channel)
Pushbutton
Sensor head
10 more 6-mA sensors
per channel
Switching
actuat
or
AC 230 V
Channel B
Channel A
DALI
KNX
KNX/DALI gateway