User Manual

Output devices
Binary output devices
Switching actuators/Modular installation system
103
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
2
Binary Output 2 x AC 230 V, 10 A
Rated contact voltage AC 230 V
2 floating relay contacts
Rated contact current 10 A
Screwless terminals for connection and through-wiring of untreated single-core, stranded or multi-
core conductors, 0.5...2.5 mm²
Bus-powered electronics
Integrated bus coupling units, bus connection via bus terminal
For insertion in flush-mounting switch and socket boxes 60 mm in diameter and 60 mm deep
Configurable behavior in the event of a bus voltage failure/recovery
Unchanged switching state of outputs in the event of system voltage failure
Integrated 8-bit scene control
Time functions: off delay, on delay, timer mode (automatic stairwell switch), night mode (lighting for
cleaning), Warning of impending off
Logical functions: Positively driven operation, logic function (1 object), logic function (2 objects), can
be inverted per output (NO contact/NC contact)
Transmitting status per channel
UP 510/..3
Range overview UP 510/..3
Product Title
Dimensions
(WxHxD)
[mm]
Stock no.
Product no.
Binary Output 2 x AC 230 V, 10 A, with mounting frame and BTI
interface
71 x 71 x 42
5WG1510-2AB03
UP 510/03
Binary Output 2 x AC 230 V, 10 A
50 x 50,9 x 41,3
5WG1510-2AB13
UP 510/13