User Manual

Input devices
Binary input devices
Combination actuators
120
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
3
Combination blind actuator, 4 x AC 230 V, 6 A, 8 x binary inputs
8 inputs for DC or AC in the range from 12 to 230 V
8 relay contact outputs locked in pairs against each other for controlling 4 × AC 230 V sunblind drives
Contact rated voltage AC 230 V
Contact rated current 6 A, p.f. = 1
Electronics powered by a AC 230 V integrated power supply
Device functional even without bus connection or if the bus communication fails
Preset on delivery for direct output control for each blind button function via momentary contact
switches connected to the inputs
Key for switching between bus and direct mode
Button for each relay contact output, for switching the output in direct mode
Selectable function for each input when using the ETS:
Switching status, send binary value
Switching on leading edge, switching Short/Long
1-pushbutton dimming, sunblind control, group control
1-bit/8-bit scene control
8-bit/16-bit value leading edge, Short/Long
16-bit floating point value leading edge, Short/Long
Or for each pair of inputs:
Acting directly on the corresponding outputs as blind button
2-button dimming with stop telegram or with cyclical sending
2-pushbutton sunblind control
Selectable blocking of each input via a corresponding blocking object
Sending of input objects after change
Selectable cyclical input object sending
Individual or shared configuration of actuator channels
Communication objects for each blind channel for driving the sun protection into the end positions or
for stopping the procedure and adjusting the blind slats in steps
Communication objects for setting position of slats and blinds in percentage information
Automatic opening of the blind slats to a preconfigured nominal setting after uninterrupted driving
down of the blind from the top to the bottom end position, with integrated 1-bit scene control for
storing and calling up (reproduction) of 2 interim blind and slat settings
Integrated 1-bit/8-bit scene control, 8 scenes can be integrated per channel
Optional "Sun" object for integration in a sunlight tracking control system
Differentiation between automatic and manual mode and with automatic switchover from automatic
to manual mode for the channel in question by pressing a bus button for manual control of the
corresponding sun protection
Manual mode taking precedence over automatic position commands
Optional central command for each device or each channel for switching the relevant channels to
automatic mode and driving the sun protection into the up or down end position
Alarm: move to safety position, Locking in this position for as long as alarm is active
Travel lock (e. g. for cleaning the outer shutter/blinds)
Status objects for each channel for querying or for automatic sending of sun protection and slat
settings as a percentage value
Optional status objects for reporting that the up or down position has been reached
Integrated bus coupling unit, Bus connection via bus terminal or contact system to data rail
Modular installation devices for mounting on TH35 EN 60715 mounting rail
Data sheet
A6V10416147
Rated voltage
AC 230 V
Rated current
6 A
Number of channels
4
Number of inputs potentialfree
8
Dimension width (1 MW = 18 mm)
8 MW
N 501/01
Stock no.
Product no.
5WG1501-1AB01
N 501/01