Solar protection, anti-glare protection, utilization of daylight
Anti-glare/solar protection actuators
179
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
6
Solar protection actuator
For control of drives with a motor for AC 230 V
Electrically interlocked relays to reverse the direction of rotation
Rated contact operating voltage AC 230 V
Rated contact frequency: 50/60 Hz
Rated contact current: 6 A
Electronics for detection of the actuation of an electromechanical and electronic limit switches
Automatic travel time determination via current measurement
Per actuator channel direct operation function on the device for driving solar protection up/down, stop
command and slat adjustment
Two status LEDs per actuator channel to indicate the direction of travel and an override
Button on the device front for deactivation of the direct mode operation and LED to indicate activation
direct mode operation
Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or
multi-core conductors, 0.5 ... 2.5 mm²
Two terminals per actuator channel for motor connection (up, down)
At least one phase connection terminal for two actuator channel each
Bus-powered electronics
Housing: plastic, color RAL 7035 (light grey), N-system
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
Type of protection: IP 20
Selectable operation mode blinds, shutter/awning, ventilation flap
Per actuator channel motion commands for moving and stopping the solar protection or for
adjustment of blind slats
Per actuator channel direct movement to a position of the sunblind and the blind slats
Per actuator channel central movement of the solar protection in manual mode and automatic mode
and delay time for Up / Down
Distinction between automatic and manual mode (position of the sunblind and blind slats) and
adjustable behaviour in sunshine
Programming and recalling preset positions 1-4 and 8-bit scene control
Adjustable behaviour in case of override (wind, rain, frost, lock, forced position, forced control, range
limitation)
Adjustable reverse pause time and delay times of the drives
Per actuator channel configurable state on bus voltage failure and start value on bus voltage recovery
Adjustable transmission of status objects (direct operation, automatic operation, curtain and slat
position, travel, calibration travel time to end positions, overriding) on request, cyclically and/or upon
change
Adjustable transmission time of the status objects after bus voltage recovery and transmission delay
between the status objects
Surveillance of device function
Rated current
6 A
N 543D..1
Solar protection actuator, 4 x AC 230 V, 6 A, with end position detection
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
all functions as N 543D..1
Data sheet
A6V11986596
Dimension width (1 MW = 18 mm)
4 MW
N 543D31
Stock no.
Product no.
5WG1543-1DB31
N 543D31
New Product