User Manual

Solar protection, anti-glare protection, utilization of daylight
Anti-glare/solar protection actuators
188
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
6
Shutter Blind Actuator, 2 x AC 230 V, 6 A
2 channels
Electrically interlocked relays to reverse the direction of rotation
Integrated electronics for detection of the actuation of an electromechanical limit switch and with
auto-calibration of the travel time from one limit switch to the other
Bus-powered electronics
Integrated bus coupling units, bus connection via bus terminal
Type of protection: IP 20
For the separate control per actuator channel of a sun protection damperdoor or window drive with a
motor for AC 230 V and electromechanical limit switches
Screw-less terminals for connection and through-wiring of untreated single-core stranded or multi-
core conductors0.5 ... 2.5 mm
2
For mounting in AP 118 automation module box or AP 641 room control box
Communication objects per actuator channel for moving the sun protection to limit positions or to
stop travel and for step-by-step adjustment of blind slats
Communication objects for moving the sun protection and adjusting blind slats directly to a new
position by positioning commands as percentage values
Automatic opening of blind slats up to a set position after the blinds have been lowered without any
stop from upper to lower limit position
Integrated 1-bit scene control for programming/recalling of 2 favored positions of blind and slats
Integrated 8-bit scene control and assignment of up to 8 scenes per channel
An optional object Sunshine” for activation/deactivation of sunlight tracking of the slats for shading
with greatest possible daylight component
Differentiation between automatic and manual mode and with automatic switch-over from automatic
to manual mode of the respective actuator channel on activation of a bus pushbutton for manual
control of the sun blind
Priority of manual mode over automatic positioning commands
Optional central command object for switching-over of all actuator channels to automatic mode and
for moving the sun blinds to the upper or lower limit position
Alarm object wind/rain/frost per channel for moving the sun protection to the configured safety
position in the event of an alarm and with blocking of travel to another position as long as alarm
pending
Travel blocking object per device or per channel for blocking the sun protection in its current position
(e.g. during cleaning of an outdoor Venetian blind)
Status objects per actuator channel for query or automatic transmission of sun blind and slat position
as percentage values
Optional status objects for signalling that the lower or upper limit position has been reached
The AP 641 room control box and AP 118 automation module box must be ordered separately.
See chapter Modular Installation System - Room control box - Module boxes.
Data sheet
A6V10416169
Rated voltage
AC 230 V
Rated current
6 A
Number of channels
2
Dimensions (W x H x D)
47,8 x 86,5 x 36,2 mm
RL 521/23
Stock no.
Product no.
5WG1521-4AB23
RL 521/23