User Manual
System products and accessories
System products
Line couplers
379
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
13
IP-Router Secure
For interconnection of bus lines or bus areas via a fast data network (Ethernet 10BaseT or 100BaseT)
with Internet Protocol (IP)
To be used as line, area and system coupler
Uses the KNXnet/IP protocol or secured access and data transmission via KNXnet/IP Secure
Up to four KNXnet/IP Tunneling connections for parallel bus access by ETS and further PC software
Assignment of the network parameters by the installer using ETS, automatically by a DHCP server in
the network
5 LEDs for display of availibility, KNX communication and IP communication
Electronics powered via “Power over Ethernet” according to IEEE 802.3af or alternatively by an
external safety extra low voltage power supply for AC/DC 24 V
Pluggable terminal block for connection of external power supply unit (not included)
Ethernet connection via RJ45 socket
Housing: plastic, color RAL 7035 (light grey), N-system
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
Type of protection: IP 20
Data sheet
A6V11656735
Dimension width (1 MW = 18 mm)
2 MW
N 146/03
Stock no.
Product no.
5WG1146-1AB03
N 146/03
Accessories for N 146/03
Product Title
Stock no.
Product no.
Electronic power supply unit, 350 mA
4AC2402
4AC2402
LOGO! Power 24 V/1.3 A
6EP3331-6SB00-0AY0
LOGO!POWER 24 V/1,3 A
Line/backbone coupler
For data exchange between two KNX bus lines with telegrams of up to 64 byte
For use as line coupler for connecting a line to the main line or as backbone coupler for connecting a
main line to the backbone line or as repeater for connecting two segments of the same line, with
electrical isolation of the two bus lines
Loadable filter table for control of the data exchange between the two bus lines
Additional loadable filter table for telegrams with LTE addressing
Detection of a communication fault on the lower-level line and signaling to the higher-level line
3 LEDs for display of availability and receipt of a telegram per line
Power supply from the main line
Modular installation devices for mounting on TH35 EN 60715 mounting rail
With bus connection to the line and to the main line via bus terminal.
Data sheet
A6V10416071
Dimension width (1 MW = 18 mm)
2 MW
N 140/13
Stock no.
Product no.
5WG1140-1AB13
N 140/13