User Manual

Home automation system
Synco living
Multi controller RRV93..
402
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
14
Multicontroller
RF-based multicontroller for precontrol of up to 2 room groups or control of ventilation plant with up to
3 stages. All inputs and outputs are also suited for universal use. The relevant data are forwarded
wirelessly by the central apartment unit QAX9...
Suited for use in heating and cooling plants for precontrol of up to 2 room groups
2 primary controllers each with a DC 0...10 V actuator
1 primary controller with a DC 0...10 V actuator and 1 primary controller with a 3-position actuator
Flow and return temperature limitation, optional control of room group pumps and DHW heating
Suited for control of 3-stage ventilation plant incl. HR bypass, with impact from humidity, indoor air
quality or CO2- level, incl. fault monitoring
Forwarding the heat / cooling demand signal to primary energy plant
RF communication based on KNX standard (868 MHz, bidirectional)
Data sheet
N2709
Operating voltage
AC 230 V
Frequency
50 Hz
Power consumption
7 VA
Control algorithm
Precontroller: PI
Communication
KNX RF-compatible, 868.3 MHz bidirectional (RF)
Indoor wireless range
30 m
Universal inputs, number
4
Universal input, signal
Digital 0/1
LG-Ni1000
DC 0...10 V
Measuring range, temperature
0...120 °C
Universal outputs, number
2
Universal output, signal
DC 0...10 V
Universal output, current
max. DC 1 mA
Relay outputs, number
4
Relay output, switching voltage
AC 24...230 V
NO - contact
Relay output, switching current
AC 0,02...2 (2) A
Mounting
On DIN rail
With screws
Degree of protection
IP30
Dimensions (W x H x D)
245 x 98 x 50 mm
RRV934
Stock no.
Product no.
BPZ:RRV934
RRV934