User Manual
Output devices
Binary output devices
Switching actuators/DIN rail mounted devices
98
Siemens Switzerland Ltd www.siemens.com/gamma 2020
Smart Infrastructure
2
Switching actuator with load current detection
One relay contact per output as switching element with load current measurement
Rated contact operating voltage AC 230 V
Rated contact frequency: 50/60 Hz
Per output with mechanical display of the switching status via slide switches, which can also be used
for direct manual operation of the switching output
Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or
multi-core conductors, 0.5 ... 2.5 mm²
One phase terminal per output
Fluorescent lamp load according to DIN EN 60669: 16 AX / 20AX (200 µF) at AC 230 V
Bus-powered electronics
Housing: plastic, color RAL 7035 (light grey), N-system
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
Type of protection: IP 20
One switching and status object per output
Selectable operating mode (normal mode, time switch mode, flashing mode),
Selectable relay mode NC contact / NO contact, On and Off delay times, control value input object
Logic operation (AND/OR/NAND/NOR/EXOR/FILTER/TRIGGER)
Selectable sending of status objects on request, cyclically and/or after a change
Selectable switching state on bus voltage failure and value of the switching object on bus voltage
recovery
Night mode for time-limited switching On of the output, and hence the illumination, at night
Variable On period at night or time switch mode, time limit in timer switch mode, warning signal prior
to imminent switching-off
Manual override, permanent OFF switching, forced control, locking mode
Counting of operating hours and counting of load cycles with threshold monitoring
Measurement of load current values with threshold monitoring and monitoring of contact faults
Integrated 8-bit scene control and linking of each output into up to 8 scenes
Surveillance of device function
Rated current
20 A
N 535D..1
Switching actuator, 4 x AC 230 V, 16/20 AX, C-Load, Load Check
Rated contact current according to DIN EN 60669: 16 AX / 20 AX (200 μF fluorescent lamp load)
all functions as N 535D..1
Data sheet
A6V11252209
Dimensions (W x H x D)
72 x 55 x 90 mm
Dimension width (1 MW = 18 mm)
4 MW
N 535D31
Stock no.
Product no.
5WG1535-1DB31
N 535D31
New Product