Data Sheet for Product

GAMMA instabus
Technical product information
May 2019
IR receiver decoder S 450 5WG1 450-7AB03
Siemens Switzerland Ltd DS02 Update: http://www.siemens.com/gamma
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a © Siemens Switzerland Ltd 2019
CH-6300 Zug Subject to change without further notice
2
Installation Instructions
The device may be used for permanent interior installa-
tions in dry locations, for mounting in ceilings, walls,
in-wall boxes or directly inside luminaires for fluores-
cent lamps.
WARNING
The device must be mounted and commissioned by an
authorised electrician.
The device must not be mounted in a box together
with 230 V devices and/or 230 V cables.
The device must not be connected to 230 V.
Ensure that there is a safe separation (SELV) of the
connected bus cable from other current / voltage carry-
ing devices and cables.
The prevailing safety and accident prevention rules
must be heeded.
The device must not be opened.
When planning and installing electrical installations,
the relevant guidelines, regulations and specifications
of the respective country must be observed.
Technical data
Power supply
KNX bus voltage: via KNX/EIB bus line
KNX bus current: 8 mA
IR transmission unit
light wave length: 890 nm
transmission freq.: 455 kHz
System reception space
wall-mounted transmitter, non-focussed beam:
5 cm to 8 m
remote control, focussed beam: max. 20m
Operating elements
Reed contact for contactless toggling between normal
operating mode and addressing mode with a program-
ming magnet: AP 590H (5WG1 590-8AH01) (not includ-
ed in delivery)
Display elements
1 red LED:
for monitoring bus voltage and for displaying normal
mode/addressing mode
1 red LED:
flashes to indicate reception of IR signals
Connections
bus line:
screwless bus terminal, Ø 0.6...0.8 mm single-core
Physical specifications
Housing: plastic
dimensions (W x H x D): 25 mm x 26 mm x 75 mm
weight: approx. 20 g
Fire load: approx. 780 kJ
Mounting:
in ceilings, walls, in-wall boxes or directly into lumi-
naires
Electrical safety
degree of pollution (according to IEC 60664-1): 2
protection (according to EN 60529): IP 20
overvoltage class (according to IEC 60664-1): III
bus: safety extra low voltage SELV DC 24 V
the device complies with EN 50 090-2-2
Electromagnetic compatibility
complies with EN 50090-2-2 and EN 61000-6-3
Environmental specifications
climatic conditions: EN 50090-2-2
ambient temperature operating: - 5 ... + 45 C
storage temperature: - 25 ... + 70 C
relative humidity (non-condensing): 5 % to 93 %
Reliability
Failure rate: 372 fit at 40 C
Markings
KNX, EIB, CE
CE mark
complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations