Data Sheet for Product

Siemens Industry, Inc.
Page 2 of 3
Specifications
Sensor
Capture zone: 290°
Mounting height: 6.5 to 13 ft (2 to 4 m), ideally 8 ft (2.5 m)
Range (at mounting height 8 ft, +72°F [2.5 m, +22°C]): Approx. 52 ft (16 m)
Dawn/twilight sensor: 0.5 to 2000 lux (factory set 7 lux)
Delay time: 5 seconds - 30 minutes (factory set 2 minutes)
Pulse mode: 1 second ON, 9 seconds OFF
Test mode: Brightness-independent mode, delay time 2 seconds
Power Supply
Bus voltage: 21 to 30 Vdc (Class 2) provided through the bus line
Bus current: 11 mA
Control Elements
One internal mode button used during commissioning:
for toggling between normal mode and addressing mode
Two external buttons used during commissioning or user adjustment:
for local setting of operating mode, brightness switching threshold, and delay
time, independent of commands on the KNX bus
Display Elements
One internal red LED used during commissioning:
for displaying normal mode (OFF) and addressing mode (ON)
One external red LED (inside the lens of the motion detector), which is used
during commissioning or user adjustment either with buttons or optional IR
remote:
for confirmation of operating mode and parameter settings.The LED pulses
during operation.
Connections
Bus line:
Bus Terminal (red-black) 20 to18 AWG solid copper
( 0.6 to 0.8 mm single core)
Strip approximately 3/16” (5 mm) of insulation
Physical Specifications Housing: plastic
Dimensions (L × W × H): Approx. 7.09” × 3.39” × 2.91”
(180 mm × 86 mm × 74 mm)
Tilting arm adjustment zone: Maximum 120°
Weight: Approximately 8.6 oz. (245 g)
Electromagnetic Compatibility Complies with EN 50090-2-2.
Environmental Conditions Ambient operating temperature: -13°F to 122°F (-25°C to 50°C)
Storage temperature: -13°F to 158°F (-25°C to 70°C)
Relative humidity (non-condensing): 5% to 93%
Certification KNX/EIB certificate
CE marking Complies with the EMC regulations (residential and commercial/industrial
buildings), and low voltage regulations