Data Sheet for Product

Page 2 of 3 Siemens Industry, Inc.
Specifications
Power Supply Bus voltage: provided through Bus Coupling Unit (BCU) UP 110/03
Control Elements Potentiometer for step less adjustment of the range between 100% and 20%
Properties
Light sensor: adjustable in steps from approximately 1 to 1000 Lux
(daylight mode to night mode)
Horizontal detection angle: 180 degrees on two levels (can be reduced to 90° on
the left or right using a detachable masking plate)
Range for P/N 5WG12552AB11
at mounting height of 3.6 feet (1.10 m):
Forward range: Approximately 33 feet (10 m)
Lateral range: 2 × approximately 19.7 feet (6 m) each side
Range for P/N 5WG12552AB12
at mounting height of 7.2 feet (2.20 m):
Forward range: Approximately 33 feet (10 m)
Lateral range: 2 × approximately 19.7 feet (6 m) each side
at mounting height of 3.6 feet (1.10 m):
Forward range: Approximately 17 feet (5 m)
Lateral range: 2 × approximately 10 feet (3 m) each side
Optical system: Fresnel lens (2 levels with 18 segments)
Connections
10-pole Physical External Interface (PEI) plug: for connection to the Bus Coupling
Unit UP 110/03
Physical Specifications Housing: plastic
Dimensions: (L × W × D): 2.56” × 2.56” × 1.18” (65 × 65 × 30 mm)
Weight: Approximately 1.6 oz. (45 g)
Installation: Snapped onto Bus Coupling Unit UP 110/03
Mounting height: 3.6 or 7.2 ft (1.10 m or 2.20 m)
Electromagnetic Compatibility Complies with EN 50090-2-2.
Environmental Conditions Ambient operating temperature: 23°F to 113°F (-5°C to 45°C)
Storage temperature: -13°F to 158°F (-25°C to 70°C)
Relative humidity (non-condensing): 5% to 93%
Certification KNX/EIB certificate
CE marking Complies with the EMC regulations (residential and commercial/industrial
buildings), and low voltage regulations