Poster

Table Of Contents
031_A6V10449313(AA)
Gamma Lighting Control – Cabinet Devices
Photo Description
Terminal
Block
Data
Rail
Notes
Output Devices
Capacity/Ratings
KNX/DALI Gateway (N 141/02)
Supports up to 64 DALI devices.
5WG1 141-1AB02
4 MW
(2.83" [72 mm])
9 mA
Max. 64 DALI devices
AC/DC 110-240V,
50-60 Hz, 7 watts
Do not connect to voltages greater than 240V; use a separate
110-240V source.
154-102 A5E02193513A
981C0C
Relay Module (N 512)
8 independent load switches for on/off control of eight separate
groups of electric devices.
5WG1 512-1CB01
8 MW
(5.67” [144 mm])
10 mA
8 circuits, each rated:
120 - 277 Vac, 20A
347 Vac, 15A
50/60 Hz
UL Listed ratings:
• 15 A @ 347 Vac (General Purpose)
• 15 A @ 347 Vac Ballast (200µF max.)
• 20 A @ 277 Vac (General Purpose)
• 20 A @ 277 Vac (Ballast (200µF max.)
• 1.5 HP @ 120 Vac (Motor)
• 3 HP @ 277 Vac (Motor)
2515014169 2515014169
908301
Blind/Shutter/Motor Controller (N 523/04)
4 load outputs. Provides manual control of blinds/shades from a
switch or touchscreen. Provides automatic sunlight tracking
control when paired with a weather station.
5WG1 523-1CB04
4 MW
(2.83" [72 mm])
5 mA
120 Vac, 6A (resistive load) 120 Vac
Circuits A and B share a common line connection, which must
be 120 Vac, and is required.
Circuits C and D share a common line connection, which may
be any voltage ≤ 120 Vac.
154-125
A5E02444230A 981202
Switching/Dimming Actuator (N 526E/02)
8 outputs for on/off and 1 to 10 Vdc dimming control of up to eight
groups (channels) of lamps.
5WG1 526-1EB02
8 MW
(5.67” [144 mm])
30 mA
8 circuits, each rated:
120 - 277 Vac, 20A
347 Vac, 15A
50/60 Hz
UL Listed ratings:
• 15 A @ 347 Vac (General Purpose)
• 15 A @ 347 Vac (Ballast)
• 20 A @ 277 Vac (General Purpose)
• 20 A @ 277 Vac (Ballast)
• 1.5 HP @ 120 Vac (Motor)
• 3 HP @ 277 Vac (Motor)
• Current sinking: 36 mA
• Dimmable electronic ballast: max. 60 ballasts at 0.6 mA ea.
154-101 2515434132
981301
Input Devices
Inputs
240505: On/off
220703: On/off, Dim/shutter/value
240A01: Value
See also Push Button Interfaces (UP 220/x1) on the Field Devices poster.
5WG1 220-2Ax 1
Computer Interface
USB Interface (N 148/11)
Enables a computer to be attached to its built-in USB socket for
addressing, ETS configuration, visualizing, logging, and diagnosis
of all KNX bus devices.
5WG1 148-1AB11
1 MW
(0.71" [18 mm])
4 mA
154-112 251515.41.60
700002
IP Interface (N148/22)
Connects a computer running ETS or visualization software to
KNX. RJ-45 socket. Offers concurrent access to the bus line from
up to five computers or other data processing equipment for ETS
configuration, visualizing, logging, and diagnosis of all KNX bus
devices.
5WG1 148-1AB22
2 MW
(1.42" [36 mm])
5 mA
(If powered from
N125/21, total
power draw is 62
mA.)
• 10Base-T (10 Mbps)
• Supports KNXnet/IP
• Simultaneous connections:
– Tunneling : 4
– Object server: 1
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• PoE is supported: 0.8 W
• SELV or NEC Class 2 power supply, AC/DC 24V 1.2 W
When Power Supply (N 125/21) or an external 24V supply is
used, current draw is 57 mA.
154-110 A5E02444759
720001
IP Controller (N 350E)
Connects a computer running ETS or visualization software to
KNX. RJ-45 socket, includes IP
interface/timer/scheduler/event/scene controller. Provides up to 80
objects for use as schedule functions, input for logic gates, event
triggers, or output of event programs (scenes). Displays date and
time.
5WG1 350-1EB01
4 MW
(2.83" [72 mm])
See footnote g
• 10Base-T (10 Mbps)
• Supports KNXnet/IP
• Simultaneous connections:
– Tunneling : 1
– Object server: 1
• Weekly scheduling
• Yearly time switching
• Real time clock
Logic Functions
• Inputs (virtual): 80
• Outputs: 30
• User-def logic gate: 30
Event Functions
• Event entries: 200
• Event trigger: 30
• Sequence Ctrl: Y, incl. 17:46 timer
Objects Suported
• 1 bit
• 1 byte
• 2 byte
• 4 byte
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• SELV or NEC Class 2 power supply, AC/DC 24V 1.75 W
When Power Supply (N 125/21) or an external 24V supply is
used, current draw is 79 mA.
154-121 251503.41.70
908701
IP Viewer (N 151)
Used to view and control KNX devices using an Internet browser.
RJ-45 socket. Incorporates a Web server for operating and
monitoring KNX systems.
5WG1 151-1AB01
4 MW
(2.83" [72 mm])
See footnote g
• 10Base-T (10 Mbps)
• Supports KNXnet/IP
• Simultaneous connections:
– Tunneling : 1
– Object server: 1
• Web server supported
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• SELV or NEC Class 2 power supply, AC/DC 24V 1.75 W
When Power Supply (N 125/21) or an external 24V supply is
used, current draw is 79 mA.
154-113 A5E01251112
909510
IP Control Center (N 152)
Used to view and control KNX devices using an Internet browser.
Webserver for standard browsers. Includes: time scheduler, logic
module, alarm function with e-mail notices and scene event recall.
5WG1 152-1AB01
4 MW
(2.83" [72 mm])
See footnote g
• 100Base-T (100 Mbps)
• Supports KNXnet/IP
Time Scheduler: Up to 300 time events per week.
Logic Functions: 1000
Alarm Messages: 250 alarm messages to 20 e-mail
addresses.
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• SELV or NEC Class 2 power supply, AC/DC 24V
nominal, current draw is 1.2 watts at 24 Vdc
2.11.1.15 L1V30048994A
983501
See also IP Router (N146/02) in the Line Coupler section. 5WG1 146-1AB02
See also Siemens BACnet Gateway (N 143) in the Gateway section. 5WG1 143-1AB01
Power Supply Unit
Input Voltage Output Rating
Power Supply Unit (N 125/01)
160 mA, with integrated choke.
5WG1 125-1AB01
4 MW
(2.83" [72 mm])
120 to 230 Vac, 50/60Hz 29 Vdc, 160 mA
2.14.4.3 251504.41.22
Power Supply Unit (N 125/11)
320 mA, with integrated choke.
5WG1 125-1AB11
4 MW
(2.83" [72 mm])
120 to 230 Vac, 50/60Hz 29 Vdc, 320 mA
2.14.4.3 251504.41.22
Power Supply Unit (N 125/21)
640 mA, with integrated choke, with additional 29 Vdc unchoked
output.
5WG1 125-1AB21
4 MW
(2.83" [72 mm])
120 to 230 Vac, 50/60Hz 29 Vdc, 640 mA
Provides separate 29 Vdc output, which can be used to power
devices requiring a separate power supply.
Device output 640 mA total, including devices on KNX network
and devices powered from 29 Vdc output.
251504.41.23 251504.41.23
Choke (N 120/02)
For operation with a Power Supply Unit without integrated choke,
or for connection to the unchoked output of the Power Supply Unit
N 125/21.
5WG1 120-1AB02
2 MW
(1.42" [36 mm])
Required if yellow/white connector from Power Supply (N
125/21) is used to power a second line.
154-100 2515044115
Data Rails and Accessories
Bus Connection Terminal (193)
2-pole, 4 plug-in connector, red/dark gray. Can only be ordered in
increments of 25.
5WG1 193-8AB01
Used as spares. A Bus Connection Terminal (193) is included
with all Gamma devices that use these connectors.
Data Rails with Integrated Connector (190/x2)
Must be ordered in multiples of 5. Integrated connector for KNX
network wiring. Terminals may be reconfigured for right or left
mounting. 24 mm (0.94") wide.
190/02, 214 mm, usable width 11 MW
5WG1 190-8AB02
214 mm (8.4")
190/12, 243 mm, usable width 12 MW
5WG1 190-8AB12
243 mm (9.6")
190/22, 277 mm, usable width 13 MW
5WG1 190-8AB22
277 mm (10.9")
190/32, 324 mm, usable width 17 MW
5WG1 190-8AB32
324 mm (12.8")
190/42, 428 mm, usable width 23 MW
5WG1 190-8AB42
428 mm (16.9")
190/52, 464 mm, usable width 25 MW
5WG1 190-8AB52
464 mm (18.3")
Data Rail without Connector (190/x 1)
Must be ordered in multiples of 5. 24 mm (0.94") wide.
190/01, 214 mm, 12 MW
5WG1 190-8AB01
214 mm (8.4")
190/11, 243 mm, 14 MW
5WG1 190-8AB11
243 mm (9.6")
190/21, 277 mm, 16 MW
5WG1 190-8AB21
277 mm (10.9")
190/31, 324 mm, 18 MW
5WG1 190-8AB31
324 mm (12.8")
190/41, 428 mm, 24 MW
5WG1 190-8AB41
428 mm (16.9")
190/51, 464 mm, 26 MW
5WG1 190-8AB51
464 mm (18.3")
Data Rail Connector (REG 191/01)
Bus connection only (2-wire), UL 916. Most common application.
Provides connection for KNX network wiring (red/black connector)
to Data Rails without Connector (190/x 1).
5WG1 191-5AB01
1 MW
(0.71" [18 mm])
Data Rail
190/x
required
REG 191/01 or REG 191/11 is required if Data Rail
190-8ABx
1 is used, and no device on the rail has both Terminal
Block and Data Rail connectors.
251505.41.06 251505.41.06
Data Rail Connector (REG 191/11)
Bus & power connections (4-wire), UL 916. Provides connection
for KNX network wiring (red/black connector) and power
(yellow/white connector) to Data Rails without Connector (190/x1).
5WG1 191-5AB11
1 MW
(0.71" [18 mm])
Data Rail
190/x
required
REG 191/01 or REG 191/11 is required if Data Rail
190-8ABx1 is used, and no device on the rail has both Terminal
Block and Data Rail connectors.
251505.41.12 251505.41.12
Cover Strip for Data Rail (192)
Used to cover unused portions of the data rail to prevent contact
with the rail.
5WG1 192-8AA01
9.5" (242 mm) Can be cut to fit.
Surge Suppressor Bus Termination Block
To be used where the occurrence of noise levels >2 kV is
expected due to the topology and electromagnetic environment of
the KNX system.
5WG1 190-8AD01
Not orderable through SAP. Contact Customer Service.
1166 1166
Event/Logic Modules
Logic Functions Event and Scene Functions
720101: 8 in/2 out AND logic.
740301: 4 in/4 out binary inverter.
740A01: 8 1-bit (on/off).
740B01: 8 1-byte (value) signals.
740C01: 4 1-bit (on/off) and 4
dimming (up/down) signals.
740D01: 4 channels. Converts 2
inputs per channel to high priority
command for compatible outputs.
Scene or Event Controller (N 305)
Provides either scene control or event program functions.
5WG1 305-1AB01
1 MW
(0.71" [18 mm])
9 mA
N/A
Events
• Event entries: 80
• Event trigger: 8
Scenes:
Scene control: 8
Only configurable for either scene or event control—the device
will not support both concurrently.
154-118 A5E01224022A 750005
Event Module (N 341)
Used to define and process event programs and schedule
programs.
5WG1 341-1AB01
1 MW
(0.71" [18 mm])
8 mA
Data Rail
190/x
required
N/A
Events
• Event tasks: 200
• Event trigger: 100
• Sequence control: Y, incl. 2-hour timer.
• 400 calendar tasks usable in up to 150 date programs.
Objects Suported
• 1 bit
• 1 byte
• 2 byte
• 4 byte
154-119 2515034134 800A06
Logic Module (N 347)
Makes it possible to perform AND, OR, NAND, and NOR logic
operations.
5WG1 347-1AB02
1 MW
(0.71" [18 mm])
8 mA
Data Rail
190/x
• 255 objects which may be
allocated as inputs or outputs.
• Up to 127 logic gates can be
defined.
N/A Supports binary (1-bit) objects only.
154-120 2515034143 800C10
Event-Schedule-Logic Controller (N 350)
Provides event programs, schedule programs (weekly scheduler),
and logic functions.
5WG1 350-1AB01
1 MW
(0.71" [18 mm])
8 mA
Data Rail
190/x
required
Inputs: 60
Outputs: 10
User-defined logic gate: 10
Events
• Event entries: 100
• Event trigger: 10
• Sequence Ctrl: Y, incl. 1:48 timer.
• 20 schedule objects controllable
by up to 100 day/time schedules.
Objects Suported: 1 bit
Supports binary (1-bit) objects only.
251503.41.45 251503.41.45 801701
See also IP Controller (N 350E) in the Computer Interface section. 5WG1 350-1EB01
See also Touch Panel (UP 588/23) on the Field Devices poster. 5WG1 588-2AB23
Line/Backbone Couplers
c
Network Connections
and Functions
000121 (coupler)
000221 (repeater)
000121 (coupler)
000221 (repeater)
IP Router (N146/02)
Connects KNX lines to Ethernet/IP. May be used to connect a
computer running ETS to KNX for downloading. Also offers
concurrent access to the bus line from up to four computers or
other data processing equipment for ETS configuration,
visualizing, logging, and diagnosis of all KNX bus devices.
5WG1 146-1AB02
2 MW
(1.42" [36 mm])
6 mA
(If powered from
N 125/21, total
power draw is
63 mA.)
• 10Base-T (10 Mbps).
• Supports KNXnet/IP.
• Simultaneous connections:
– Tunneling : 4
– Object server: 1
• Line coupler (routing) supported.
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• PoE is supported: 0.8 W
• SELV or NEC Class 2 power supply, AC/DC 24V, 1.2 W
When Power Supply (N 125/21) or an external 24V supply is
used, current draw is 57 mA.
154-107 A5E02444614
001002
Gateways
Siemens IP Gateway KNX/BACnet (N 143)
Gateway for integration of KNX systems into BACnet control
systems. May be used to connect a computer running ETS to
KNX for downloading. 250 KNX communication objects.
5WG1 143-1AB01
4 MW
(2.83" [72 mm])
10 mA
(If powered from
N 125/21, total
power draw is
55 mA.)
(see Notes)
Use one of the following:
• 29 Vdc from Power Supply (N 125/21)
• SELV or NEC Class 2 power supply, AC/DC 24V, 1 W
When Power Supply (N 125/21) or an external 24V supply is
used, current draw is 45 mA.
2.11.1.16
L1V30058373A
983601
IntesisBox® BACnet/IP Server - KNX
Gateway for integration of KNX systems into BACnet control
systems. 500 KNX communication objects.
IBOX-BAC-KNX-A
~6 MW
(4.21" [107 mm])
See footnote g
(see Notes)
Power supply:
9-30 Vdc, 1.4W
24 Vac, 125 mA
Included with
LinkBox software
Included with
LinkBox software
IntesisBox® BACnet/IP Server - KNX
Gateway for integration of KNX systems into BACnet control
systems. 3,000 KNX communication objects.
IBOX-BAC-KNX-B
~6 MW
(4.21" [107 mm])
See footnote g
(see Notes)
Power supply:
9-30 Vdc, 1.4W
24 Vac, 125 mA
Included with
LinkBox software
Included with
LinkBox software
IntesisBox® Modbus Server (Slave) TCP/RTU - KNX
Gateway for integration of KNX systems into Modbus control
systems. 500 KNX communication objects.
IBOX-MBS-KNX-A
~6 MW
(4.21" [107 mm])
See footnote g
(see Notes)
Power supply:
9-30 Vdc, 1.4W
24 Vac, 125 mA
Included with
LinkBox software
Included with
LinkBox software
IntesisBox® Modbus Server (Slave) TCP/RTU - KNX
Gateway for integration of KNX systems into Modbus control
systems. 3,000 KNX communication objects.
IBOX-MBS-KNX-B
~6 MW
(4.21" [107 mm])
See footnote g
(see Notes)
Power supply:
9-30 Vdc, 1.4W
24 Vac, 125 mA
Included with
LinkBox software
Included with
LinkBox software
Cabinets
Gamma Lighting Control Enclosures
Support Gamma Lighting system components and other panel-
mounted devices that snap into DIN rails. NEMA Type 1 lighting
control panel with removable dead front, EN60715-TH35-7.5-1mm
DIN rails, removable/reversible door with key lock. Each DIN rail
accomodates 20 module widths (MW)
b
.
20" × 20", two DIN rails, fits 40 MW total.
LCC-2020-MV
20" W × 4" D × 20" H
(51 × 10 × 51 cm)
20" × 28", three DIN rails, fits 60 MW total.
LCC-2028-MV
20" W × 4" D × 28" H
(51 × 10 × 71 cm)
20" × 44", five DIN rails, fits 100 MW total.
LCC-2044-MV
20" W × 4" D × 44" H
(51 × 10 × 112 cm)
NOTES:
a) When entering a Product Number in SAP, do not use spaces or dashes. For example, Product Number 5WG1 141-1AB02 is entered as 5WG11411AB02.
b) 1 MW (Gamma N-system module width) = 0.71" (18 mm). Some Gamma documents may refer to SU (N-system standard unit) rather than MW.
c) If the backbone is IP, use the IP Router (N 146/02).
d) Used by the primary line.
e) Used by the secondary line.
f) For both the primary and secondary lines.
g) Where KNX bus load is not indicated, assume 10 mA per device.
A6V10443516 A6V10425806
Needed to support devices that only have a Data Rail bus
connection (N 261, N301, N 341, N 347, N 350).
Install Power Supply on the Data Rail to provide KNX bus to
modules without a KNX terminal.
Optional parts: REG 191/01 or REG 191/11, Cover Strip for
Data Rail (192).
f
(2)
e
Data Rail
190/x
required
154-109
154-109
Primary line provides power for the device.
• AND
• Invert
• Partition control
Data Rail
190/x
required
Needed to support devices that only have a Data Rail bus
connection (N 261, N301, N 341, N 347, N 350).
Install Power Supply on the Data Rail to provide KNX bus to
modules without a KNX terminal.
Optional part: Cover Strip for Data Rail (192).
The top DIN rail in each enclosure is commonly reserved for low-
voltage modules. If no low voltage modules exist in the
enclosure, the top DIN rail may be used for line voltage
modules.
Network Connections and Functions
us203a_n261us203a_n261
154-103
2515054115
154-122
Applications 740A01, 740B01 and 740C01 are used for
combining/separating switch commands based on up to 16
combinations of position of up to 4 movable partitions.
251503.41.13N/A
2515.08.41.32
2515.08.41.20
Application Program Description
(APB)
Documentation Product Numbers
Product Features
Dimensions
b
Technical
Product Info
(TPI)
Install
Instructions
(BMA)
d
Logic Module (N 301)
Applies logic operations to group addresses received.
Selected applications support partition control.
1 MW
(0.71" [18 mm])
4 mA5WG1 301-1AB01
Line/Backbone Coupler (N 140/03)
Provides a data connection between two KNX bus lines and also
isolates those bus lines from each other so that each bus line
operates independently. Can be used as a line coupler, backbone
coupler or repeater in KNX networks.
Line/Backbone Coupler (N 140/13)
Provides a data connection between two KNX bus lines and also
isolates those bus lines from each other so that each bus line
operates independently. Can be used as a line coupler, backbone
coupler or repeater in KNX networks.
5WG1 140-1AB13
2 MW
(1.42" [36 mm])
• 6 mA on
primary line
• 8 mA on
secondary line
5WG1 140-1AB03
1 MW
(0.71" [18 mm])
• 6 mA on
primary line
• 8 mA on
secondary line
(see Notes)
Monitored outputs must provide 24V AC/DC. To monitor dry
contacts, provide an external 24V AC/DC power supply, or use
Pushbutton Interface 5WG1 220-2ABx1.
Bus Connection
5WG1 261-1CB01
Voltage: AC/DC 24V
Current (per circuit):
• 3.5 mA (24 Vac)
• 6 mA (24 Vdc)
External Power
Supply Required
Current or Power
Draw on KNX
Bus
Product Number
a
Binary Input Module (N 261)
Four inputs for monitoring low voltage inputs. Each input can be
assigned various tasks depending on the application program
used.
2 MW
(1.42" [36 mm])
3 mA
Data Rail
190/x
required