Brochure

24
System data
Bus connection
Radio frequency 315 MHz (Asia), 868 MHz (EU countries
and China), 902 MHz (USA and Canada)
and 928 MHz (Japan)
Ranges
… dependent on the
nature of the building
Range reduction due to wall materials
against free-field propagation (300 m):
Wood, plaster, uncoated glass,
without metal 0 – 10%
• Brick, pressed wood 5 – 35%
Concrete with iron reinforcement
10 – 90%
Bus devices
Number of transmitters/
transmit protocols
500/minute
(99.9% transmission probability)
Telegram duration 0.6 ms
Topology Routing or direct communication between
sensor/actuator
Power supply
System voltage
Battery-free, maintenance-free wireless
modules (sensor/actuator), and variants
of line-connected actuators, repeaters and
gateways
Transmission
Transmission technology Bidirectional and unidirectional possible,
serial
Baud rate 125,000 bit/s
Device properties
Standby current demand 0.08 A
Protection class Device-dependent