Room sensors for tempera-
ture, humidity and air quality
Mounting guidelines for sensors measuring room
temperature, relative humidity and air quality
Mount sensors in rooms at a height of approx. 1.5 m
and a distance of at least 50 cm from the nearest wall
Do not expose to direct sunlight
Do not mount on external walls
Do not place in alcoves or on shelves
Avoid locations near to air flows and heat sources
Reliable detection of room climate is only possible
if the doors and rooms are closed
Do not cover with curtains