Data Sheet for Product

Cable Specifications and Sourcing
6
Siemens Industry, Inc.
Gamma Lighting Control Wiring Guidelines
125-3596
2013-01-08
Table 5:
H-TP18-CMP and H-TP18-CMP-Box
Wire and Cable Specification - Required Information.
Description
HVAC CBL 18AWG,STR,1TP,CMP, BLUE JACKET
Specifications
Number of pairs
1
Resistance DCR: 6.92 Ω/1000 ft nominal
Gauge and stranding
18 AWG (7 × 26)
Capacitance: N/A
Primary insulation type
PRPVC
Twists per foot: 4 nominal
Nominal Insulation thickness
0.009”
Jacket Material: PRPVC
Color code
BLK/WHT
Nominal Jacket thickness: 0.015”
Shield type(Tape, Braid)
N/A
Jacket color: Blue
Shield coverage
N/A
Nominal O.D.: 0.155”
Tape
N/A
Packaging: 1000 ft
Drain wire
N/A
UL type: CMP
Braid construction
N/A
Voltage rating: 300V
Impedance(1, 10, 100 Mhz)
NA
Temp rating: 75°C minimum
Print Legend: NORTHFLEX® H-TP18-CMP “DI, DO, AI, AO” 18 AWG 2C 75°C CMP (UL)
C(UL) (Plus Mfg E#)
NOTE: Sequential footage markers (1000 descending to 0) required.