Data Sheet for Product

Page 2 of 3
Siemens Building Technologies, Inc.
All luminaires controlled by an N 141/02 can be
dimmed to the setting “Dimming value on emergency”
even when they are not affected by a line voltage or
DALI power failure. This allows you to maintain all
luminaires and self-contained emergency luminaires at
the same brightness level.
During “Emergency Operation”, luminaires will not
respond to any on/off or dim commands and they
cannot be commissioned.
Application Programs
07 B0 KNX/DALI Gateway 981C0C
Specifications
Power Supply
Bus voltage: 21 to 30 Vdc (Class 2) provided through the bus line
Bus current: 5 mA
Electronics and DALI output:
Integrated power supply for AC/DC 110-240V, 50-60 Hz (Do not connect to
voltages greater than 240V – use a separate 110-240V source.)
Power consumption: max. 7 W
Inputs/Outputs
Bus communication on N-system data rails or KNX bus terminal
Line voltage connection: 3-pole (PE(earth ground), N, L)
DALI output (according to IEC 60929):
Max. 64 DALI devices with
> 8k ohm input impedance
DALI bus voltage: approx. 19 Vdc, floating, short-circuit-proof
Control Elements
One mode button for use during commissioning only:
for toggling between normal mode/addressing mode
One push button for use during commissioning or manual operation:
for toggling between bus operation/manual mode
Two push buttons for use during commissioning or manual operation:
for switching all electronic ballasts ON/OFF
Display Elements
One red LED:
for displaying the mode that was selected with the mode button.
One green LED:
for displaying the presence of operating voltage
One yellow LED:
for displaying bus operation/manual mode
One red LED:
For indicating ON/OFF status when in manual mode
Blinking to indicate communication or lamp failure
Connections
Line voltage and DALI interface: plug-in terminals, insulation strip length 3/8“ (10 to
11 mm)
The following conductor cross-sections are permitted:
20 to 12 AWG solid (0.5 to 3.3 mm2 single-core)
20 to 12 AWG stranded (0.5 to 3.3 mm2 multi-core)
20 to 12 AWG (0.5 to 3.3 mm2 ) finely stranded, untreated
20 to 16 AWG (0.5 to 1.5 mm2) finely stranded, with connector sleeve
Bus line:
Pressure contacts on data rail
Bus Terminal, 18 to 20 AWG solid copper (Ø 0.6 to 0.8 mm single core)