Brochure
Selection and
catalog information
Type Model Catalog no. PU (unit, set, M) PKG/VPE PG Price (€)
N 525D11 Switch/dim actuator
2x DALI Broadcast
5WG1525-1DB11
Broadcast applications All the important information
at a glance
Tunable White
Broadcast application – two rooms (one channel per room)
Product features Switch/dim actuator N 525D11, 2x DALI Broadcast
• Control capacity for up to 20 DALI ECGs
per DALI output
• With an integrated net device for power supply
of the device electronics and DALI outputs
• With DALI output power of approximately
19 V, potential-free and short-circuit proof
• LED display to display operating states
and the following error notifications:
‒ Defective lights
‒ External voltage on DALI line
‒ Short circuit DALI line
‒ No ECG found
• Buttons on the front of the device
to deactivate direct operation and LED
to show status in direct operation
• Pair of buttons per DALI outlet for joint
switching on/off and dimming of all
connected lights in direct operation
• Building site function that enables in
factory condition the switching on/off
of building site lighting using a bus key
and an actuator, even if these devices
are not yet launched with the Engineering
Tool Software (ETS)
• With DALI-2 certification
Control functions
• Color temperature control (Tunable White)
• Seven dimming curves can be set up to
optimize dimming behavior of lights
• Selectable operation type normal operation,
1 or 2-step timer operation, blinking
• Adjustable actuating value input object
for switching on/off depending on
actuating value
• Central switching with separate adjustable
delayed switching on/off
• Adjustable dimming and color temperature
value on switching on
• Status object switching and/or status object
dimming and color temperature value
• Integrated 8-bit scenario control with up
to eight scenario assignments per outlet
• Two selectable logical connections
(AND, OR, NOT/AND, NOT/OR, EXCLUSIVE/OR,
FILTER, TRIGGER)
• Night operation object can be added
for time-limited switching on of the outlet,
for example lighting
Override functions
• Manual override ON
• Duration OFF
• Locked mode
• Central override
• Override on or off
Diagnostic functions
• Operating hours counter
with threshold monitoring
• Switching cycle counter
with threshold monitoring
• Status and error notifications