Data Sheet for Product

Page 2 of 3
Siemens Industry, Inc.
Application Programs
25 S1 Brightness Controller 909601
The following functions may be selected in ETS:
Type of control (On only, Off only, On/Off or
constant light level)
When constant light level control is selected, the
number of additional (slave) groups of luminaires
which can be dimmed to different values
If the measured brightness value is transmitted at
a time interval or only after a change of value
If the switching and dimming commands are
transmitted at a time interval,
If the setpoint value for brightness control is set
using a parameter or a communication object,
Controller behavior after a power loss.
The setpoint value calibration to the currently
measured brightness value can be triggered through a
special communication object.
Brightness control may be temporarily deactivated to
permanently set the light level brighter or darker.
Specifications
Power Supply Bus voltage: 21 to 30 Vdc (Class 2) provided through the bus line
Bus current: Maximum 15 mA
Measuring Range 0 to 2000 Lux (with a reflection degree from the working surface of about 30%)
Control Elements
One mode button:
for toggling between normal operating mode and addressing mode.
Display Elements
One red LED (beneath the optical fiber rod):
for displaying normal operating mode (OFF) and addressing mode (ON), and for
use during commissioning or user adjustment through an IR remote control.
Connections
Bus line:
Bus terminal (red–black): 20 to 18 AWG solid copper wire
(Ø 0.6 to 0.8 mm single core).
Strip approximately 3/16"(5 mm) of insulation.
Physical Specifications
Brightness Controller UP 255/11
Housing and cover: Plastic
Dimensions without cover (L × W × H): 1.97” × 1.38” × 0.55”
(50 mm x 35 mm x 14 mm)
Weight: Approximately 1.06 oz (30 g) •
Installation: in a junction box that complies with DIN 49073–GB-T-M1E1 (02/90),
Ø 2.36” (60 mm), depth 1.57” (40 mm). May also be attached directly to the
mounting surface with screws.
Brightness Controller AP 255/12
Housing: Plastic
Dimensions: Ø 2.95” (75 mm), height 1.02” (26 mm)
Weight: Approximately 1.76 oz (50 g)
Installation: Surface mounting
Electromagnetic Compatibility Complies with EN 50090-2-2.
Environmental Conditions Ambient operating temperature: 23°F to 113°F (-5°C to 45°C)
Storage temperature: -13°F to 158°F (-25°C to 70°C)
Relative humidity (non-condensing): 5% to 93%
Certification KNX/EIB certificate
CE marking Complies with the EMC regulations (residential and commercial/industrial
buildings), and low voltage regulations