Brochure
36 37
Status messages of DALI
operating devices
On/off, dimmer setting, length of operati-
on, lamp error
Control input Galvanically isolated from the line voltage
(potential-free); all bus devices operate on
different phase conductors.
Power supply
System voltage DC V DALI bus voltage: approx. DC 16 V, poten-
tial-free, short-circuit-proof, where 0 V can
range from -4.5 V to +4.5 V, and 16 V is in
the range of 9.5 V to 22.5 V.
Acc. to DIN VDE 0100, Part 520, Section
528.11, main circuits and associated auxil-
iary circuits can be laid together, even if
the auxiliary circuits conduct a lower volt-
age than the main circuits.
Maximum system
current
Maximum current of the central interface
supply is around 250 mA.
Each connected device can consume a
maximum of 2 mA.
Power supply No dedicated power supply is needed.
Transmission
Transmission technology serial, asynchronous
Baud rate 1,200 bit/s
Device properties
Protection class EN 60529 (DIN VDE 0470 -1) and
DIN EN 50102
Safety measures Basic insulation required according to
IEC 60 928; safety extra-low voltage (SELV)
is intentionally not used in order to permit
cost-effective installation
EMC requirements EN 50081/VDE 0839-81 and
EN 50082/VDE 0839-82
Ballast standards Safety (EN 61347)
Functionality (EN 60929)
Line current harmonics (EN 61000- 3 -2)
Radio interference suppression from
9 kHz to 300 MHz (EN 55015: 2006 +
A1:2007)/CDN measurement
Immunity (EN 61547)
Conditions for use
Ambient temperature
for reliable lamp ignition
From -20 °C (preheating of both lamp
filaments)
Permissible temperature
range for reliable lamp
operation
-20 °C to +75 °C
Bus systems