Presence detectors
(incl. brightness sensors)
Mounting guidelines for presence detectors
Make sure that the workplace is right in the detection
zone of the presence detector – without any obstacles
such as shelves, plants, glass walls, etc. blocking the
detector
Keep in mind that moving machines, plants and animals
in the detection zone will be interpreted as movement
Avoid sources of rapid changes in temperature or light,
such as fans, incandescent or halogen lamps; air flows
and light in the detection zone simulate movement
Mount at least 50 cm away from cables and radiators
Mounting guidelines for presence detectors with
brightness sensors
Avoid light sources that switch on or off, such as TVs,
in the detection zone; they simulate movement
Avoid light sources with a high infrared component;
they distort the daylight measurement
Make sure that the brightness sensor measures only
indirect, reflected light; direct sunlight distorts the
measurement results
Avoid shiny surfaces that are highly reflective
Keep in mind that thermal protection glass can influ-
ence the daylight measurement; the tripping value
will be lower
Mounting guidelines