Room sensors for tempera-
ture, humidity and air quality
Mounting guidelines for room sensors
Mount room sensors in the living area at a height of
approx.1.5 meters and a distance of at least 50 cm
from the nearest wall
Do not expose to direct sunlight
Do not mount on external walls
Do not place in alcoves or on shelves
Avoid placing near lamps or fans
Avoid walls in front of radiators
Do not mount in the immediate vicinity of doors
Do not cover with curtains
To ensure accurate readings, it is a good idea to
keep the following in mind during installation:
Clearances between the cable (4)
or plastic hose and the installa-
tion pipe (5) need to be sealed.
Otherwise, inefficient air circula-
tion will occur, causing measur-
ing errors.
When mounting on massive walls
(1) made of steel, concrete, etc.,
you need to place thermal insula-
tion (2) between the room sensor
(3) and the wall.