Room sensors for tempera-
ture, humidity and air quality
Mounting guidelines for room sensors
■
Mount room sensors in the living area at a height of
approx.1.5 meters and a distance of at least 50 cm
from the nearest wall
■
Do not expose to direct sunlight
■
Do not mount on external walls
■
Do not place in alcoves or on shelves
■
Avoid placing near lamps or fans
■
Avoid walls in front of radiators
■
Do not mount in the immediate vicinity of doors
■
Do not cover with curtains
To ensure accurate readings, it is a good idea to
keep the following in mind during installation:
Clearances between the cable (4)
or plastic hose and the installa-
tion pipe (5) need to be sealed.
Otherwise, inefficient air circula-
tion will occur, causing measur-
ing errors.
When mounting on massive walls
(1) made of steel, concrete, etc.,
you need to place thermal insula-
tion (2) between the room sensor
(3) and the wall.
Mounting guidelines