Flyer
Technical data
Type Description
RS 510/23
RL 513/23
RL 512/23
Binary output RS 510/23, binary output RL 513/23,
switching actuator RL 512/23
• Selectable operating mode (normal operation,
timer operation) for each output
• Selectable relay mode (NC contact/NO contact)
for each output
• Status object as an optional addition for each output
• Adjustable On and Off delay times for each output
• Selectable logic operation (AND/OR) of two communi-
cation objects for each output
• Adjustable switching state on bus voltage failure and
recovery for each output
• Optional addition of “Night mode” object for time-limited
switching On of the output (and hence the illumination)
at night for each output
• Adjustable On period in night or time switch mode
• Selectable post-triggering of the On period (On period
extension) in time switch mode
• Selectable warning signal prior to imminent switching Off
by means of three short Off and On cycles (flashing) at
night or in time switch mode
• Selectable function: manual override of an output
including additional communication object
• Selectable function: forced control for switching an
output On or Off in forced mode, including additional
communication object
• Selectable function: operating hours count with threshold
monitoring of operating hours
• Selectable function: switching cycle count with threshold
monitoring of switching cycles
• Integrated 8-bit scene control and incorporation of each
output into up to 8 scenes
Binary output RS 510/23
• 2 x AC 230 V, 10 A (resistive load)
Binary output RL 513/23
3 x 6 A
Switching actuator RL 512/23
• 1 x AC 230 V, 16 AX
• One relay contact as switching element
• Fluorescent lamp load per DIN EN 60669-1:16 AX
(200 μF) at AC 230 V
• Switching current in AC1 operation (p.f. = 0.8)
per DIN EN 60947-4-1: 20 A at AC 230 V
• Switching current in AC3 operation (p.f. = 0.45)
per DIN EN 60947-4-1: 16 A at AC 230 V
RS 520/23
Shutter blind actuator RS 520/23,
shutter blind actuator RL 521/23
• For control of sun protection, door or window drive with
a motor for AC 230 V and electromechanical or electronic
limit switches
• Electrically interlocked relays for reversing direction
of rotation
• Integrated electronics for detection of the actuation
of an electromechanical limit switch and with auto-
calibration of the travel time from one limit switch
to the other
• Communication objects for each actuator channel
for driving the sun protection into the end positions
or for stopping the procedure and adjusting the blind
slats in steps
• Communication objects for directly adjusting the sun
protection and blind slats to a position with position data
as a percentage (as precisely as permitted by the drive
mechanism)
• Automatic opening of the blind slats to a preconfigured
nominal setting after uninterrupted driving down of the
blind from the top to the bottom end position
• Integrated 1-bit scene control for storing and calling up
(reproduction) of 2 intermediate blind and slat settings
• Integrated 8-bit scene control and incorporation of each
channel in up to 8 scenes
• Optional “Sun” object for activation/deactivation of
sunlight tracking control of the blind slats for shading
with the greatest possible amount of daylight
• Differentiation between automatic and manual mode as
well as automatic switchover from automatic to manual
mode of the respective actuator channel on activation
of a bus pushbutton for manual control of the associated
sun protection
• Priority of manual mode over automatic positioning
commands
• Optional central command for switching over all
channels to automatic mode and for moving the
sun protection to the upper or lower end position
• Alarm object “Wind, “Rain” and “Frost” per channel for
moving the sun protection to the configured safety
position and with blocking of travel to another position
as long as the alarm is pending
• Object “Block motion” for each device or channel
for blocking the sun protection in its current position
(e.g. during cleaning of an outdoor blind)
• Status objects for each actuator channel for query
or automatic transmission of sun protection and slat
position as percentage values
• Optional status objects for signaling that the lower
or upper end position has been reached
Shutter blind actuator RS 520/23
• 1 x AC 230 V, 6 A (resistive load)
Shutter blind actuator RL 521/23
• 2 x AC 230 V, 6 A (resistive load)
RL 521/23
7