Brochure

Heating, ventilation and air conditioning - room temperature control
Room temperature controllers with integrated sensing
i-system
238
Siemens Switzerland Ltd www.siemens.com/gamma 2021
Smart Infrastructure
7
Base modules with KNX for CO2 measurement
Base module with maintenance and recalibration-free CO2 sensor to plug onto a front module
1 analog input to connect temperature sensors with NTC 10k sensing element to measure room, floor,
or ceiling temperature
2 multifunctional binary inputs to connect window contacts or buttons
Power supply via KNX bus, bus load < 5 mA
Communication: KNX S-Mode, KNX PL-Link
Ventilation control across 3 settable switching steps for relative humidity & CO2 concentration, and 3
switching signal objects On/Off, or one positioning signal object 0…100% to control a ventilation actor
Temperature control as continuous control (PID algorithm) for pure heating operation, heating and
cooling operation, and adjustable positioning variable as continuous positioning signal 0…100%, or as
pulse-width modulated (PWM) switching signal On/Off
Via setpoints for room temperature and relative humidity, and CO2 concentration, adjustable via KNX
bus
Adjustable commissioning and control parameters
Integrated bus coupler with programming button and LED
Data sheet
N1411
Voltage supply
KNX bus
Measuring range
CO2: 0...5000 ppm
Analog inputs, number
1
Analog inputs
Passive temperature sensor NTC 10k
Digital inputs, number
2
Digital inputs
Potential-free contacts
Warranty
5 Years
AQR2576..
Range overview AQR2576..
Mechanical design
Dimensions
(WxHxD)
[mm]
Stock no.
Product no.
EU (CEE/VDE)
71 x 71 x 45
S55720-S207
AQR2576NF
IT (3 Modular)
71 x 71 x 45
S55720-S209
AQR2576NG
UK (British Standard)
71 x 71 x 45
S55720-S208
AQR2576NH
US (UL)
64 x 110 x 45
S55720-S210
AQR2576NJ