Technical Specification Sheet Document No. A6V10455751 December 3, 2014 GAMMA Stand-alone Lighting Control Products Siemens Product Number Leviton Product Number Technical Specification Sheet Number For dimming incandescent, magnetic low-voltage, halogen, neon/cold cathode lighting. 1920 W/1920 VA @ 120 Vac, 50/60 Hz.
Siemens Product Number Leviton Product Number Technical Specification Sheet Number LCO-2310-MT OSW12-M0W G7732A LCO-2315-HB OSWHB-I0W G7734A LCO-2320-COR OSWLR-I0W G7733A Power input: 120/230/277 Vac, 50/60 Hz Control input: 24 Vdc, 5 mA from LCO sensors Power output: 24 Vdc, 150 mA to LCO sensors and LCS LV wall switches Relay load rating: 20A fluorescent/incandescent @ 120V; 20A fluorescent @ 230-277V; 1 hp @ 120V, 2 hp @ 240V LCR-2410-ODO OSP20-D0 G8226B With Dry Contact Relay Power input
Photo Description Siemens Product Number Leviton Product Number Technical Specification Sheet Number LCW: Line Voltage Decora Wall Switches with Occupancy Sensors (Stand-alone) Wall Box PIR Occupancy Sensor, 180°/2100 sq ft at 4 ft 120/277 Vac, 60 Hz, neutral not required, external power pack not required, Decora wall plate not included (001-ODS0D-IDI) Single pole, single relay, manual on time delay 30 sec to 30 min.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. APOGEE and Insight are registered trademarks of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2014 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel.
PE100-1 Product Specifications PE100-1 Power Extender APPLICATION PE100-1 Power Extender Leviton’s PE100-1 Power Extender allows a dimming zone’s power handling capacity to be extended to a full 1920W/VA on 120V input power. It allows a zone to dim or switch a fully loaded circuit of incandescent and magnetic low voltage loads only.
Product Specifications PE100-1 ......................... SPECIFICATIONS Wiring Diagram 1A: Single Feed Wiring Application w/Controller Warranty: Limited 2-Year Warranty (Load) Single Feed Wiring Line Hot can be controlled by one circuit breaker as long as the total load does not exceed the Power rating of the Extender circuit breakers.
PE200-1/ PE200-7 Product Specifications PE200-1/PE200-7 Power Extenders APPLICATION FEATURES & BENEFITS • Works with Mark X or Hi-lume® 120V (Cat. No. PE200-1) and 277V (Cat. No.
PE200 Wiring Diagram 1A 120V Single Feed Wiring Application w/Mark X™ Ballast ) Used if Dimmer/Switch has Neutral connection ( Hot (Black) (120VAC) 120V Mark X™ Type Dimmer SWITCH HOT HOT LOAD CONTROL NEUTRAL D3206/08 Controller/Dimmer NEUTRAL Single Feed Wiring Line Hot can be controlled by one circuit breaker as long as the total load does not exceed the rating of the circuit breaker.
PE200 Wiring Diagram 3A 277V Dual Feed Wiring Application w/Mark X™ Ballast ) Used if Dimmer/Switch has Neutral connection ( Hot (Black) Line 1 (120VAC) (Load) Neutral 1 (White) Power Extender HOT Neutral Neutral Line SWITCH HOT NEUTRAL LOAD CONTROL NEUTRAL Dual Feed Wiring The Input control circuit and the Output load circuit can be supplied by two circuit breakers on a single phase or by two separate phases.
PE200 MOUNTING All Power Extenders must have 4-1/2" spacing above and below each unit for proper ventilation and heat dissipation (refer to figure 3). Line voltage wiring should be at least 6ft away from sound or electronic equipment wiring. Mount Power Extender to wall box with “TOP” facing up as follows: For Wall Box Mounting (refer to figure 1), for Flush Mounting (refer to figure 2) and for Panel Mounting (not shown), proceed as follows: a.
PE400-1 Product Specifications PE400-1 Power Extender APPLICATION FEATURES & BENEFITS • Works with electronic low voltage and incandescent • Emulates the characteristics of the dimmer that it is connected to in terms of dimming range and resolution • Works with any Dimensions Multi-zone Controller/Dimmer to extend load capacity for electronic low voltage loads on any zone 2.06 MOUNTING 4.50 2.80 4.
PE400-1 .........................
PRODUCT SPECIFICATIONS Timer Switches for Energy Management LTB30-1L LTT60-1L Better than ever – Leviton Decora Timer Switches offer advanced features, superior accuracy and contemporary aesthetics. Our robust selection provides convenient timed control of lighting and motor loads in homes, offices, schools, hotel rooms and other small commercial applications. An easy upgrade, automatic timers help reduce energy costs, improve security and add convenience.
AGENCY STANDARDS AND COMPLIANCE WARRANTY INFORMATION Complies with FCC Part 15, Class B n CSA Certified (File #152105) n UL Listed VPT24, LTBxx Series and LTTxx Series (File #E-328809) n UL Listed 6651 and 6652 (File #E-148771) n Limited Five-Year Warranty n DIMENSIONAL DRAWINGS VPT24-1P LTBxx-1L Series 1.40 (35.6) 1.75 (44.5) 1.40 (35.6) 1.75 (44.5) 4.13 (104.9) 4.13 (104.9) 2.71 (68.8) 2.72 (69.1) 0.19 (4.9) .038 (9.7) 1.73 (44.0) 6651/6652 1.35 (34.2) 0.23 (5.8) 1.19 (30.2) 2.76 (70.
WIRING DIAGRAMS 5-Button Timer Switches LTBxx Series Single Pole Wiring Application Timer Switch White Black Hot (Black) Green Ground Red Yellow/Red Black Insulating Label Line 120 VAC, 60Hz Load White Neutral (White) LTBxx Series LTBxx Series 3-Way Wiring with Coordinating Remote Switch, VP0SR-10 (no LED) Application 3-Way Wiring with Matching Remote Switch, VP0SR-1L (w/LED) Application Coordinating Remote Switch (no LED) Matching Remote Switch (with LED) BK BK WH (unused) Green Ground
DERATING/MAXIMUM CAPACITY In multi-gang installations, all devices must be derated in accordance with the following chart: Cat No.
product data Self-contained pIr ceiling Mount occupancy Sensor BaSIc opEratIoN The ODC0S-I uses passive infrared (PIR) detection technology to monitor a room for occupancy through a segmented Fresnel lens. This specialized lens divides the field-of-view into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches its lighting loads ON. The lights will remain ON as long as there is an occupant moving through the sensor zones.
product data INStaLLatIoN The ideal location for the Self-Contained Occupancy Sensor unit is in a ceiling area that provides a full view of the space with an unobstructed path to the entrance way(s), but out of line from hallway traffic. The sensor should be positioned at least 6 feet from HVAC registers to prevent false triggering. The ODC0S-I may be mounted directly to a three or fourinch octagon box. The sensor wires directly to the lighting fixtures.
PRODUCT DATA OSFHU Passive Infrared Fixture Mount High Bay Occupancy Sensor BASIC OPERATION Passive Infrared Technology (PIR) is used to sense occupancy by comparing the infrared energy from an object in motion and the background space. PIR sensors minimize false ON from background environmental conditions such as air movement to provide reliable detection of lineof-sight motion.
PRODUCT DATA FEATURES Quicksnap: built into the 1/2” nipple, this locking mechanism allows for the fastest and easiest mounting not requiring a threaded lock-nut Reduce time and materials: easily reach the ballast at either end of the fixture without requiring more wire or connectors with the included 42” wire leads Fast, easy time delay setting: can be set at any time without requiring power to the sensor; time delay is variable from 30s-20m Instantly verify fixture operation and wiring connections: “insta
FIELD-OF-VIEW 9.1m (30 ft) High Bay 360˚ Top View 6.1m (20 ft) 3m (10 ft) 0 3m (10 ft) 6.1m (20 ft) OSFOA 9.1m (30 ft) 0 Side View 6.1m (20 ft) 9.1m (30 ft) 12.2m (40 ft) 3m 9.1m 6.1m (30 ft) (20 ft) (10 ft) 0 OSFHU Wiring Diagram 3m 6.1m 9.1m (10 ft) (20 ft) (30 ft) Hot (Black) Black Aisle Top View Red Line 120-277-347 VAC 50/60Hz 9.1m (30 ft) 6.1m (20 ft) Black Sensor White Load 3m (10 ft) White 0 Neutral (White) 3m (10 ft) 6.1m (20 ft) 9.1m (30 ft) 0 Side View 6.1m (20 ft) 9.
PRODUCT DATA SPECIFICATIONS ELECTRICAL Input Voltage 120-230-277-347VAC; 240/480VAC (-I4W models) Operational Frequencies 50/60Hz Load Rating 800VA @ 120VAC Ballast 1200VA @ 277VAC Ballast 1500VA @ 347VAC Ballast 2000VA @ 480VAC Ballast Motor: 1/4 HP Load @ 120V Standby Power Consumption 120V – 130mW – .13W 277V – 450mW – .45W 347V – 460mW – .
OSC04-IOW OSC15-IOW Occupancy Sensor Infrared Ceiling Sensor The all-digital & microprocessor based OSCxx-I is the most advanced infrared ceiling sensor available. Self-calibrating sensitivity and timer allow the installer to “install & forget.
Product Specifications OSC04-IOW OSC15-IOW ......................... PRODUCT SPECIFICATIONS RANGES OSC15 Models Part Number OSC04-IOW OSC15-IOW Lens Type Coverage Additional Features High Density Extended Range 450 sq. ft. 1500 sq. ft Photocell Photocell TOP VIEW 20 10 CONTROLS PIR (Infrared Sensitivity): High to low. Timer Adjustment (Manual): 30s - 30 min. - Factory set 10 min.
product data Multi-technology ceiling occupancy Sensor • Self-Adjusting: Internal microprocessor continually analyzes, evaluates and adjusts the sensitivity and time delay. Performance is kept at a maximum and user complaints are eliminated. • Custom off-white color matched for shaded ceilings. • Fast, Simple Installation: Easy ceiling mount, three wire connection (low voltage) and twist-lock sensor attachment for 360° rotation and flexibility.
product data dip SWitcH SettingS SWitcH Bank a A1 N/A A2 N/A A3 Manual Mode A4 Walk-Thru Disable Bank B B1 Override to On B2 Override to Off B3 Test Mode B4 LED Disable diMenSionS SWitcH FunctionS oFF Multi-Tech PIR Auto Adapting Enabled Walk-Thru Enabled SWitcH SettingS on Single Tech Ultrasonic Auto Adapting Disabled Walk-Thru Disabled Auto Mode Auto Mode OFF’ON’OFF LEDs Enabled Lights forced On Lights forced Off Enter/Exit Test Mode LEDs Disabled 1.571” 4.
product data BaSIc operatIon Occupancy sensors have two tasks: 1) Keeping the lights ON while the room is occupied, and 2) Saving energy by keeping the lights OFF while the room is unoccupied. Leviton’s OSCxx-RMW sensors combine the benefits of both PIR and U/S technologies for unrivaled performance and reliability. Additionally, the sensor is designed with an isolated relay contact; which enables the sensor to interface with other systems (example: BAS, HVAC or any dry-contact capable device or system).
product data HoW tHe oScxx-r autoMatIcaLLy adaptS Example An installer accidentally leaves the sensor in the 4 sec. timer test mode and the lights may go off or on every 4 sec. Adaptive Reaction The sensor automatically resets the timer to the preset time delay after 15 minutes of test mode False-On - The sensor incorrectly turns the lights on. The sensor detects movement in the corridor or hallway and the room lights turn on.
pHySIcaL WIrInG Sensor OSPxx Series Power Pack Bas (Or Other Building Management System) Red Black Blue (Control) Red Black To BAS System Black N/C – Brown Common – Green Blue +24v - Red Com - Black Control - Blue N/C - Brown Common - Green N/O - Brown/white N/O – Brown/White Load Blue Hot (Black) Red Blue To BAS System Black Black Blue Occupancy Sensor Line 120-277-347 VAC 60 Hz White N/C – Brown Common – Green N/O– Brown/White White Neutral (White) SpecIFIcatIonS Power Requirements
oScxx-rMW product data Leviton Manufacturing co., Inc. Lighting & energy Solutions 201 N. Service Rd. Melville, NY 11747-3138 Tech Line: 1-800-824-3005 Fax: 1-800-832-9538 www.leviton.com/les visit our Website at: www.leviton.com/les © 2011 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
product data BaSIc operatIon Occupancy sensors have two tasks: 1) Keeping the lights ON while the room is occupied, and 2) Saving energy by keeping the lights OFF while the room is unoccupied. Passive Infrared (PIR) is an excellent and precise technology for initially turning the lights ON, but lacks sensitivity for minor motion at distances. Ultrasonic (U/S) technology provides maximum sensitivity with continuous reflective high frequeny waves. This is opitmal for keeping the lights ON.
product data adjuStMent range MountIng Bracket dIMenSIonS Base Cover Sensor Mounting Base Long Range Lens 6.43 inch Mounting Base 4.23 inch 4.67 inch Base Cover Sensor dIp SWItcH SettIngS SWItcH Bank a A1 N/A A2 N/A A3 Manual Mode A4 Walk-Thru Disable Bank B B1 Override to On B2 Override to Off B3 Test Mode B4 LED Disable 2.
product data BaSIc operatIon Specifically designed for long, relatively narrow spaces such as warehouse aisle and corridors, the OSWHBI0W Occupancy Sensor provides long range and high sensitivity. The OSWHB-I0W Occupancy Sensor is a “high bay” lens. This lens provides coverage up to 55 ft. when mounted 20 ft. above the floor. Can be mounted lower if needed. The mounting base, provided with the sensor, allows quick and easy mounting in corners, on walls or on ceilings.
product data MountIng Bracket adjuStMent range dIMenSIonS 60° Mounting Base 85° Base Cover Long Range Lens 6.43 inch 4.23 inch 4.67 inch Sensor 2.
product data BASIC OPeRAtIOn Specifically designed for long, relatively narrow spaces such as hallways and corridors, the OSWLR-I Occupancy Sensor provides long range and high sensitivity. The OSWLR-I Occupancy Sensor utilizes a “long range” lens. This lens provides coverage up to 100 ft. when mounted 10 ft. above the floor. Can be mounted lower if needed. The mounting base, provided with the sensor, allows quick and easy mounting in corners, on walls or on ceilings.
product data mOuntIng BRACket AdjuStment RAnge dImenSIOnS 60° Mounting Base 6.43 inch 4.23 inch 4.67 inch Base Cover 85° Long Range Lens Sensor dIP SwItCH SettIngS SwItCH BAnk A A1 N/A A2 N/A A3 Manual Mode A4 Walk-Thru Disable BAnk B B1 Override to On B2 Override to Off B3 Test Mode B4 LED Disable 2.
product data oSp/oSa power pack Series Containing both a 24VDC supply and a 20A line voltage relay for most models, the Leviton compact Power Pack provides low voltage power and line voltage control for Leviton Occupancy Sensors. Versions include Auto-ON and ManualON inputs for occupancy sensors, Hold-ON and Hold-OFF capabilities, and a local input for momentary or maintained dry contact switches.
product data FEaturES oSp20-0d0/oSp20-Nd0 • Self-contained transformer and relay • Internal voltage regulator – regulated 24VDC current, 150mA output • Fast installation - mounts inside or outside junction box, or inside fluorescent ballast cavity with a simple twist-on nut • Single or multiple luminaire control • Zero crossing circuitry • UL 2043 Plenum Rated • Companion Add-A-Relay provides additional capacity (OSA20-R00) • NAFTA compliant (OSP20-ND0) • Made in USA compliant (OSP20-DA0) dIMENSIoNS 3.
OSP20-RxH Bi-Level Switching OSP20-RxH Bi- Level Switching N Yellow Zone 1 – Auto ON H Occupancy Sensor Orange Orange/Yellow Black Blue White White/Blue Local SW 1 Auto ON Blue Green Blue Brown/White Brown +24VDC Red Com Black LOAD 1 LOAD 2 Yellow Zone 2 – Manual ON Orange Orange/Yellow Black Blue White White/Blue Local SW 2 Momentary or Maintained Switches Manual ON Blue Green Blue Brown/White Brown Red Black Com SIgNaL typE LINE VoLtagE wIrES Line 120-230-277VAC (OSP20-Rx0
product data SpEcIFIcatIoNS ELEctrIcaL Line Voltage 120-230-277 VAC Relay Rating HVAC Relay: 0.5A @ 120VAC, 1.0A @ 30VDC ENVIroNMENtaL Operating Temperature Range 32°F to 104°F (o°C to 40°C) Relative Humidity 0% to 90% non-condensing, for indoor use only otHEr Construction Case: high impact, UL rated plastic Relay: class B (130°C) insulating material; silver alloy contacts Wire: 6” leads, 18AWG input; LV connections: 7” leads 22AWG Dimensions 2.400”H x 3.811”W x 1.432”D (60.96mm x 96.80mm x 36.
PRODUCT DaTa Power Base adaptor PROBLEM: Hard ceilings with limited access for low-voltage wiring installations SOLUTIOn: Leviton’s Power Base Adaptor DESCRIPTIOn Leviton’s OPB15-0DW is a self-contained transformer and relay adaptor with a patent-pending technology that converts any Leviton low-voltage ceiling or wall sensor to line voltage. The OPB150DW conveniently mounts to a standard 2.125” deep x 4” octagon, 2.
PRODUCT BULLETIn OPB15 Power Base adaptor SPECIFICaTIOnS ELECTRICaL Input Voltage Output Voltage 120-277 VAC @ 50/60Hz 24 VDC, 40mA nominal, full-wave rectified and filtered, unregulated.(Each Leviton sensor contains an internal voltage regulator.) Load Rating 15A Incandescent, Electronic or Magnetic Fluorescent Ballast; 3/4 HP at 120V Wire Designation Line-Black, Load-Blue, White-Neutral Power Consumption Lights On: 120V - 1.58W, 277V - 2.34W (base only) Lights Off: 120V - .27W, 277V - 1.
56081-2I Le vit on Ca t a log # : 56081-2I D e scr ipt ion: 3 Am p, 24 Volt , Decora Plus Rocker Double- Throw Ct r - OFF Mom ent ary Cont act Single- Pole AC Quiet Swit ch, Com m ercial Grade, Self Grounding, Back & Side Wired, - I vory Pr odu ct Fe a t u r e s: Ground: Feat ure: Am perage: Volt age: Term inat ion: Act uat or Mat erial: Body Mat erial: St rap Mat erial: Color: Warrant y: Self Grounding Double- Throw Ct r - OFF Mom ent ary Cont act 3 Am p 24 Volt Back & Side Therm oplast ic Therm oplast ic
56081-2W Le vit on Ca t a log # : 56081-2W D e scr ipt ion: 3 Am p, 24 Volt , Decora Plus Rocker Double- Throw Ct r - OFF Mom ent ary Cont act Single- Pole AC Quiet Swit ch, Com m ercial Grade, Self Grounding, Back & Side Wired, - Whit e Pr odu ct Fe a t u r e s: Ground: Feat ure: Am perage: Volt age: Term inat ion: Act uat or Mat erial: Body Mat erial: St rap Mat erial: Color: Warrant y: Self Grounding Double- Throw Ct r - OFF Mom ent ary Cont act 3 Am p 24 Volt Back & Side Therm oplast ic Therm oplast ic
PRODUCT DATA Decora® Wall Switch PIR Occupancy Sensor BASIC OPERATION The ODS10-ID uses passive infrared (PIR) detection technology to monitor a room for occupancy through a segmented Fresnel lens. This specialized lens divides the field-of-view into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches the lights ON. The lights will remain ON as long as there is an occupant moving through the sensor zones.
ODS10 PRODUCT DATA FEATURES • Fits in standard wallbox and replaces single-pole wall switch. Gangable with other units. • Low-profile design eliminates obtrusive “scanning-device” look. Elegant Decora wallplates complement any interior for sleek aesthetics; uses Decora wallplates and coordinates with Leviton’s popular line of Decora wiring devices.
DIMENSIONAL DIAGRAMS 1.75” (44.4mm) Mounting Yoke 0.48” (12.6mm) 1.30” (33.0mm) Vandal Resistant PIR Lens 1.35” (34.4mm) Patented Blinders Control Panel, Cover Removed BLINDERS 4.06” (103.2mm) 2 4 7 LED Window and Light Sensor 10 3 TIME 2.60” (66.2mm) 2.61” (66.
PRODUCT DATA INSTALLATION The ODS10-ID may replace a single-pole wall switch mounted in a standard wallbox. The unit must be properly grounded in order to operate. The unit’s integral blinders may be used to restrict the fieldof-view to prevent unwanted detection of hallway traffic. It should be positioned at least 6 feet away from HVAC registers. Note that whenever the unit is powered up, it will take approximately one minute to begin normal operation.
PRODUCT DATA ODS0D-ID-TD BASIC OPERATION The ODS0D uses passive infrared (PIR) technology to monitor a room for occupancy through a segmented Fresnel lens. This specialized lens divides the field-ofview into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches two separate lighting loads ON. The lights will remain ON as long as there is an occupant moving through the sensor zones.
PRODUCT DATA ing tape required. • Time delay adjustment for delayed-OFF time settings of 30 seconds, 5, 10, and 30 minutes. Allows customized adjustments to maximize energy savings. • Vandal resistant PIR lens. • False detection circuitry. • Light Sensor adjustable Ambient Light Override ranges from approximately 2FC (20 LUX) to 500+FC (5000+ LUX). • Manual-ON/auto-OFF mode for installations where manualON switching is required but auto-OFF switching is still desired for CEC Title T24 energy savings.
FIELD-OF-VIEW The ODS0D provides a 180° field-of-view with a maximum coverage area of approximately 2100 square feet. The maximum sensing distance in front of the sensor is 40 feet, and at each side is 30 feet. The “minor motion” zone detects relatively small body movements and allows the lights to stay ON even though a person may not be moving or walking around the room. The remainder of the field-of-view, the “major motion” zone, exhibits a lesser degree of sensitivity and requires larger movements.
PRODUCT DATA SPECIFICATIONS DIMENSIONAL DIAGRAMS ELECTRICAL 1.75 (44.4 mm) Line Voltage 120-230-277 VAC Power Consumption 120V - 110mW 277V - 270mW Operational Frequency 50/60Hz Wire Designation Primary Relay— No. 16 AWG leads: Line—Black Load—Blue Ground—Green Secondary Relay— N0.
PRODUCT DATA Decora® Wall Switch Multi-Technology Occupancy Sensor OSSMT-MD/GD The PIR sensors provide immunity to false ON through a specialized Fresnel lens which divides the field-ofview into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches the lights ON. The Ultrasonic (U/S) sensors provide maximum sensitivity and range in difficult spaces with irregular shaped rooms and partitions that can block the PIR field-of-view.
OSSMT PRODUCT DATA FEATURES • Fast, simple Installation: Fits in a standard wall box and replaces a single-pole wall-switch; neutral and no neutral options available. Sensor can be ganged together with other units in a multiple-switch wall plate. • Low-profile design eliminates obtrusive “scanning-device” look. Elegant Decora wallplates complement any interior for sleek aesthetics; uses Decora wallplates and coordinates with Leviton’s popular line of Decora wiring devices.
INSTALLATION The OSSMT is preset to deliver optimum performance in a wide variety of applications without requiring any adjustments during installation. Exclusive self-adjusting operating features will automatically compensate for real-time occupancy patterns to provide maximum convenience and energy savings. The unit may replace a single-pole wall switch mounted in a standard wall box. The OSSMT-MD must have a neutral and be properly grounded in order to operate.
OSSMT PRODUCT DATA LEVITON SPECIFICATION SUBMITTAL JOB NAME: JOB NUMBER: CATALOG NUMBERS: Leviton Manufacturing Co., Inc. Lighting & Energy Solutions 201 N. Service Rd. Melville, NY 11747-3138 Tech Line: 1-800-824-3005 Fax: 1-800-832-9538 www.leviton.com/les Leviton Manufacturing of Canada, Ltd. 165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9 • Telephone: 1-800-469-7890 • FAX: 1-800-563-1853 Leviton S. de R.L. de C.V. Lago Tana 43, Mexico DF, Mexico CP 11290 • Tel.
PRODUCT DATA Dual Relay Decora® Wall Switch Multi-Technology Occupancy Sensors OSSMD-FT BASIC OPERATION The PIR is used to detect motion and turn lights ON, while either technology is used to keep lights ON while occupied. This allows the Ultrasonic (U/S) to be set to higher sensitivity levels minimizing false OFF conditions. The PIR portion gives immunity to false ON through a specialized lens that divides the field-ofview into sensor zones.
OSSMD PRODUCT DATA FEATURES • Provides automatic lighting control for two separate banks of fluorescent, incandescent, or lowvoltage lighting from a single unit. • The second relay is a manual-ON only with a maximum 30 minute time-out for maximum energy savings to comply with CEC Title 24 • The OSSMD-FT is intended to control a light circuit and a fan. The button on the sensor provides ON control for both circuits and OFF for lighting circuits only.
TOP VIEW FIELD-OF-VIEW The OSSMD provides a 180° field-of-view with a maximum coverage area of approximately 2400 square feet. The maximum major motion sensing distance in front of the sensor is 40 feet, and side to side is 30 feet. The “minor-motion” zone detects relatively small body movements and allows the lights to stay ON even though a person may not be moving or walking around the room. This zone is approximately 40 feet by 20 feet.
PRODUCT DATA DIMENSIONAL DIAGRAMS SPECIFICATIONS ELECTRICAL Operational Frequency U/S Operating Frequency Wire Designation Load Rating 1.75in/44.4mm 120-230-277 VAC -FT 120V 220mW 277V 430mW 50/60Hz -MD 210mW 410mW -GD 140mW 360mW 0.48in/12.6mm 1.30in/33.0mm 1.35in/34.4mm 40kHz Primary RelayNo. 16 AWG leads: Line-Black Load-Blue Ground-Green White-Neutral (where provided) Primary Relay: Fluorescent: 1200VA @ 120V 2700VA @ 277V Incandescent: 800W @ 120V Secondary RelayNo.
PRODUCT DATA Decora® Wall Switch PIR Occupancy Sensor with LED NightLight NightLight High Level BASIC OPERATION The passive infrared (PIR) sensor detects motion from a heat-emitting source within its field-ofview to automatically switch lights ON and OFF, offering the same performance features as the ODS family of occupancy sensors. OSSNL has the ability to reduce (dim) and turn off the “Guide Light” function with a simple dial setting.
PRODUCT DATA OSSNL FEATURES CONT. • To comply with T24, red LED indicator light flashes when sensor detects motion to verify detection is active. • Time Delay adjustment for delayed-OFF time settings of 30 seconds (for walking test), 10 minutes, 20 minutes, and 30 minutes. Allows customized adjustments to maximize energy savings.
DIAGRAMS Blinder adjustment levers 30M 1H 30S 4 7 4 AU TO 10 2H TIM E MA N BLINDERS RANGE ON MODE/NL DIM Control Panel Cover OSSNL Sensor Features 0.48 (12.6 mm) 2.60 (66.2 mm) 4.06 (103.2 mm) 2.61 (66.3 mm) 1.35 (34.4 mm) Vandal Resistant Lens with PIR and LED Night Light LED Indicator and Light Sensor Dimensions Night Light Leviton Mfg. Co., Inc. Lighting & Energy Solutions 201 N. Service Rd. Melville, NY 11747-3138 Tech Line: 1-800-824-3005 Fax: 1-800-832-9538 www.leviton.
PRODUCT DATA SPECIFICATIONS ELECTRICAL Line Voltage 120-230-277VAC Power Consumption 120V, Nightlight OFF - 190mW 120V, Nightlight ON max - 350mW 277V, Nightlight OFF - 250mW 277V, Nightlight ON max - 410mW Operational Frequency 50/60Hz Wire Designation Line - Black Load - Blue Ground - Green Neutral - White Load Rating Fluorescent: 1200VA @ 120V, 2700VA @ 277V Incandescent: 800W @ 120V, Motor – 1/8 HP @ 120V ENVIRONMENTAL Operating Temperature Range 32° to 122°F (0°C to 50°C) Storage Temperatur