PE200
Leviton Mfg. Co., Inc.
59-25 Little Neck Pkwy • Little Neck, NY 11362-2591 • Tech Line: 1-800-824-3005 • Fax: 1-800-832-9538
Visit our Website at: www.leviton.com
© Copyright 2003 Leviton Manufacturing Co., Inc. All rights reseved. G-6723A/G3
JOB NAME:
JOB NUMBER:
CATALOG NUMBERS:
SPECIFICATION SUBMITTAL
1900 Box
Raised Cover
Mounting Screws
(4 Places)
Power
Extender
Power Extender
Wallplate
TOP
2 Gang Raised Cover
1900 Box
Raised Cover
Mounting Screws
(4 Places)
TOP
2 Gang Raised Cover
Power Extender
Wallplate
Power
Extender
Figure 2: Flush Mounting
MOUNTING
All Power Extenders must have 4-1/2" spacing above and below each unit for proper ventilation and heat dissipation (refer to figure 3). Line
voltage wiring should be at least 6ft away from sound or electronic equipment wiring. Mount Power Extender to wall box with “TOP” facing up
as follows: For Wall Box Mounting (refer to figure 1), for Flush Mounting (refer to figure 2) and for Panel Mounting (not shown),
proceed as follows:
a. The enclosure must be in accordance with all local and national electrical codes.
b. Leviton DOES NOT recommend using a door to enclose the front of a panel, since this restricts airflow to the controls.
c. If mounting multiple controls in an enclosure:
• Ambient timperature within an enclosure “MUST REMAIN BETWEEN”32
o
-104
o
F
(0
o
-40
o
C).
• If not mounting in a metal enclosure, all units “MUST” be mounted in a wall box.
d. To improve heat dissipation of controls, remove the faceplate from the unit.
TOP
TOP
4-1/2" (11.4 cm)
Minimum
4-1/2" (11.4 cm)
Minimum
Figure 3: Front View Spacing
Figure 2: Flush Mounting
Figure 1: Surface Mounting