Data Sheet for Product

Table Of Contents
Leviton Mfg. Co., Inc. Lighting & Energy Solutions
201 N. Service Rd. Melville, NY 11747-3138 Tech Line: 1-800-824-3005 Fax: 1-800-832-9538 www.leviton.com/les
© 2011 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
OSSMD
FIELD-OF-VIEW
The OSSMD provides  a  180° field-of-view with a 
maximum coverage area of approximately 2400 
square  feet.  The  maximum  major  motion  sens-
ing
distance  in  front  of  the  sensor  is  40  feet, 
and  side  to  side  is  30  feet.  The  “minor-motion” 
zone detects relatively small body movements
and allows the lights to stay ON even though a
person may not be moving or walking around the
room.  This  zone  is  approximately  40  feet  by  20 
feet.
H
Phase 1
Neutral (White)
Sensor
Black
Ground
Blue
Red
Red
Load
Load
White
Line
120-230-277VAC
50/60Hz
Line
120-230-277VAC
50/60Hz
H
Phase 1
Neutral (White)
Sensor
Black
Ground
Blue
Red
Red
Load
Load
WIRING DIAGRAMS
OSSMD-MD/OSSMD-FT OSSMD-GD
OSSMD Field-of-View (in feet)
TOP VIEW
30
SIDE VIEW
20 40
0
0
20
20
30
4
5
0
Major Motion, PIR Major Motion, U/S
Major Motion, PIR Major Motion, U/S
INSTALLATION
The OSSMD mounts in a standard single-gang wall
box and replaces two single-pole wall switches
that control two separate lighting loads. The unit
must be properly grounded in order to operate.
The unit’s integral blinders may be used to restrict 
the field-of-view to prevent unwanted detection
of hallway traffic. The OSSMD should be posi-
tioned at least 6 feet away from HVAC registers. 
Note that whenever the unit is powered up, it
will take approximately 1 minute to begin normal
operation.
Note: Ground wire must be connected.
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor 1 Sensor 2
Black
Black
Blue
Red
Blue
Red
Red
Red
Green
Ground
Green
Ground
Line
120-230-277VAC
60Hz
White
White
MULTI-LOCATION