Technical Manual
G
B
Binary Output N 562 5WG1 562-1AB01
2 x 230 V AC / 10 A
Issued: March 2003
Product and Applications Description
The binary output N 562 is a N-system DIN-rail mounted de-
vice. It has two outputs to switch on/off two separate groups
of electric loads.
Each of the outputs can be assigned various tasks depending
on the application program used, i.e. the binary output N 562
consists of the device (hard-ware) and its application programs
(software).
Appropriate application programs are available for the different
tasks the binary output N 562 can handle; e.g. for direct on/off
switching, time switch (non-delayed on, delayed off), delayed
on/off switching or for controlling electrothermal actuators.
With the ETS (EIB Tool Software) the application program is
selected, its parameters and addresses are assigned appropri-
ately, and downloaded to the binary output N 562.
Additional Informations
http://www.siemens.de/gamma
Example of Operation
instabus EIB
binary output N 562
channel B
channel A
2 L
1
L1 L2 N
electric loads
e.g. fluores-
cent lamp
3 L
4
5 L
6 L
bus coupling unit
load circuit
AC 230/400V
Technical Specifications
Power supply
via bus line
Outputs
· number: 2 outputs (volt free contacts)
· rated voltage: AC 230 V, 47 ... 63 Hz
· rated current: 10 A resistive load
· switching current at AC 230 V:
0,01 ... 10 A resistive load
· switching current at DC 24 V:
- 10 A resistive load,
- 4 A inductive load (L/R = 7 ms)
· switching characteristic: set in parameter list according to
application program
Switching power at AC 230 V
· at incandescent lamp load: max. 1000 W
· at fluorescent lamp (FL) load:
- uncorrected FL, cos j = 0,5: max. 500 W
- parallel corrected FL, cos j = 1 (at Ctot <= 14 µF):
2 x 58 W or 3 x 36 W or 6 x 18 W
- twin-lamp circuit, cos j = 1: max. 1000 W
- Osram ECG for 58 W FL: max. 10 units
- Osram ECG for 36 W FL : max. 15 units
- Osram ECG for 18 W FL : max. 20 units
Connections
· load circuit, physical:
strip insulation for 9 ... 10 mm
permissible conductor types/cross sections:
- 0,5 ... 2,5 mm² single core or flexible conductor,
8 mm ultrasonically compacted
- 0,5 ... 2,5 mm² flexible conductor with terminal pin,
crimped on gas tight
- 0,5 ... 1,5 mm² flexible conductor with connector sleeve
- 1,0 and 1,5 mm² plain flexible conductor
· load circuit, electrical:
- plain flexible conductor, min. 1 mm²:
current carrying capacity max. 6 A
- all other conductors, min. 1,5 mm²:
current carrying capacity max. 10 A
- the load circuits have to be saved by a circuit breaker
with A or B characteristic with a maximum nominal cur-
rent of 10 A!
V
WARNING
JJJJJJJJJJJJJJJJJJJ
When looping through the L-conductor (connection
blocks 3 and 2, 6 and 5), take care that the maxi-
mum connection current of 10 A (as governed by the
maximum permissible printed conductor load) is not
exceeded!
· bus line:
- pressure contacts on data rail
Physical specifications
· N-system DIN-rail mounted device,
width: 2 SUs (1SU = 18mm)
· weight: approx. 160 g
Electrical safety
· protection (according to EN 60529): IP 20
Environmental specifications
· ambient temperature operating: - 5 ... + 45 °C
· ambient temperature non-op.: - 25 ... + 70 ° C
· relative humidity (non-condensing): 5 % to 93 %
Location and Function of the Display and
Operator Elements
A1
A2
A4
A3
A5
Figure 1: Location of the display and operator elements
A1 LED for indicating normal operating mode (LED off) and
addressing mode (LED on); upon receiving the physical
address the device automatically returns to normal op-
erating mode
A2 Learning button for switching between normal operat-
ing mode and addressing mode and for receiving the
physical address.
A3 Type plate
A4 Screwless plug-in terminals for connecting load circuits
A5 Label for noting the physical address
Mounting and Wiring
· The device may be used for permanent interior
installations in dry locations within distribution boards or
small casings with DIN rail EN 60715-TH35-7,5.
V
WARNING
JJJJJJJJJJJJJJJJJJJJJJJ
· The device may be built into distribution boards (230/400V)
together only with appropriate VDE-devices.
· The device must be mounted and commissioned by an
authorised electrician.
· A safety disconnection of the device must be possible. Es-
pecially if the device is connected to different phases.
· Free DIN rail areas with sticked-in data rails must be cov-
ered with covers, order no. 5WG1 192-8AA01.
· The prevailing safety rules must be heeded.
· The device must not be opened.
· For planning and construction of electric installations, the
relevant guidelines, regulations and standards of the re-
spective country are to be considered
General Notes
· Any faulty devices should be returned to the local Siemens
office.
· If you have further questions about the product,