User Manual

16/12
Siemens ET D1 · 2018/2019
16
Technical Information
Socket Outlets
SCHUKO socket outlets with overvoltage protection
SCHUKO socket outlets with residual-current protection
Overview
For the protection of electronic devices against overvoltages
(in overvoltage category II according to DIN VDE 0110-1).
Surge arresters of requirement category D according to
E DIN VDE 0675-6 and 0675-6/A1:1996-03.
Features:
Overvoltage protection with monitoring device and discon-
nector
Visual function indicator (glow lamp, green)
Visual fault display (glow lamp red, no disconnection)
With retaining ring for installation in switch boxes (60 mm Ø,
40 mm deep)
Technical specifications
1)
Only required if not already available in the system.
Schematics
Schematics
Tested E DIN VDE 0675-6; EN 61643-11 and
IEC 61643-1
Rated voltage U
N
230 V / 50 Hz
Surge arrester rated voltage
(maximum permissible opera-
tional voltage)
U
C
255 V / 50 Hz
Rated discharge current (8/20) I
SN
L (N) -> PE, L
L + N -> PE
3 kA
5 kA
Combined surge U
OC
L (N) -> PE, L
L + N -> PE
6 kV
10 kV
Protection level U
p
L -> N
L(N) -> PE
1.5 kV
1.5 kV
Response time t
A
L -> N
L(N) -> PE
25 ns
100 ns
Series fuse
1)
16 A gL/gG or B 16 A
Temperature range J
-25 … +40 °C
Terminals
3 double terminals,
each up to 2.5 mm
2
also suitable for through-wiring
L
N
PE
L
N
L
PEN
TN S network TN C network
(with formation
of TN S network
on the socket outlet)
TT network