LV dimmers, for electronic transformers, 20 to 600 W, 20 to 525 VA, for two way switching (5TC8284)
16
Technical specifications
Schematics
Power supply Mains connection 230 V (2-wire method), rated voltage: 230 V AC, 50 Hz
Protection against short-circuits
Reversible operating electronic fuse
Protection against overloads With additional temperature cutout, which shuts down the dimmer in the event of an overload and only
resupplies it automatically with power when the overload is eliminated after the device has sufciently
cooled down
Load output
Number Two terminals for two-way switching ( and )
Rated voltage 230 V AC, 50 Hz
Rated load (up to 35 °C ambient temperature)
- Incandescent lamps 20 ... 600 W
- HV halogen lamps 20 ... 600 W
- LV halogen lamps with electronic transformer 20 ... 525 W
- Note Does not support connection of:
Energy-saving lamps
Magnetic transformers
- Maximum connected load at ambient temperature
Warning: The connected load must be
reduced by 25 %, depending on oper-
ating conditions
For mounting on wood, Rigips, gas
concrete or cavity walls
For installation in multiple combina-
tions or surface-mounting enclosures
If using highly thermally insulating
materials (e.g. glass wool), it may be
necessary to reduce the connected
load even further
Terminals
4 screw terminals with anti-slip terminal body, the following conductor/cross-sections are permissible:
0,5 ... 4.0 mm² solid
0,5 ... 2.5 mm² nely stranded, with or without end sleeve (without insulating collar, gas-tight crimp
connection)
Mechanical specications
Enclosure Plastic
Dimensions Modular width: 71 mm x 71 mm, mounting depth: 32 mm
Weight Approx. 95 g
Fire load Approx. 1000 kJ
Mounting Installation in device boxes 60 mm Ø, 40 mm deep according to DIN 49073-1
Electrical safety
Pollution degree (acc. to IEC 60664-1) 2
Degree of protection (acc. to EN 60529) IP20
Overvoltage category (acc. to IEC 60664-1) III
Standard According to EN 60669-2-1
EMC requirements According to EN 60669-2-1, EN 61000-6-3 and EN 61000-6-1
Environmental specications
Ambient operating temperature –5 ... +45 °C
Storage temperature –25 ... +70 °C
Relative humidity (non-condensing) 5 ... 93 %
Approvals VDE certication
I2_11961
-10 20 40 60
20
0
40
60
80
100
800
100
Ambient temperature [°C]
Relative connected load [%]
L
PE
N
L
1
2
I2_11965a
1
2
3
3
4
4
Outer conductor connection
Load connection / corresponding conductor
Load connection / corresponding conductor
Trimpotentiometer for load balancing
230 V
AC
~
2 3