User Manual
16/43
Siemens ET D1 · 2018/2019
Technical Information
Motion detectors
Comfort motion detector tops
16
Programming
Operating modes
On the Comfort motion detector top, three different operating
modes can be set by means of a switch:
• Continuous OFF
For this mode, the switch must be moved to the position.
The lighting is continuously switched off. Switching is not pos-
sible by means of extension units.
• Automatic mode
For this mode, the switch must be moved to the position. If
a motion is detected, the Comfort motion detector top
switches on in dependence of brightness and if the motion is
no longer detected, it is switched off a
fter the set delay time
has expired. Switching is possible by means of extension
units.
• Continuous ON
For this mode, the switch must be moved to the position.
The lighting is continuously switched on. Switching is not pos-
sible by means of extension units.
Locking of the switch
The switch can be interlocked in the automatic mode switching
position using a locking clip:
• Set the device to automatic mode
• Carefully remove the slider with a screwdriver
• Insert the locking clip
Adjusting the delay time
The delay time determines how long the lighting remains
switched on if a motion is no longer detected. The delay time can
be set within a range of 10 s to approx. 30 min. The setting is car-
ried out non-linearly, longer times can only be specified within a
relatively rough grid.
To mod
ify the delay time, turn the controller in the desired
direction.
If the Comfort motion detector top has switched on, each further
detected motion results in a retriggering of the delay time. This
means, the delay time starts anew.
The Comfort motion detector t
op does not support a forced shut-
down. This means, continuous motion within the sensing field
results in continuous lig
ht.
I2_08795
1 2 3
Mode of operation
“Continuous OFF”
1
2
3
1
2
3
Mode of operation
“Automatic mode”
Mode of operation
“Continuous ON”
I2_08796
1
2
1
2
Slider
Screwdriver
1
2
3
I2_08797
1 2 3
30 min
10 min 3 min
10 s
Empf.
Overtravel time controller
Brightness controller
Sensitivity controller
1
1
1
2
3