Installation Instructions

Installation Instructions
Document No. 129-404
April 13, 2020
OpenAir
®
GCA Spring Return
Rotary Electronic Damper Actuator
Item Number: 129-404 Rev. KA Page 1 of 7
a. Actuator
b. Self-centering shaft adapter
b. Oversized shaft adapter
c. Position indicator
d. Shaft adapter locking clip
e. Position indicator adapter
f. Mounting bracket
g. Mounting screws
h. 3 mm hex key
i. Conduit adapter 1/2-inch
(Not available to GCAxxx.xP models)
j. 500 ohm resistor (GCA15x.xx only)
Figure 1. Parts of the GCA Actuator.
Product Description
Describes the steps for direct-coupled mounting of the
OpenAir GCA spring return electronic damper actuators.
Product Numbers
GCAx
Warning/Caution Notations
WARNING:
CAUTION:
Required Tools
10 mm (13/32-inch) open-end wrench
Drill and 4 mm (5/32-in) drill bit
3 mm hex key (provided)
Phillips screwdriver
Small flat-blade screwdriver
Marker or pencil
Additional for oversized shaft adapter:
10 mm (13/32-inch) socket wrench
6 mm hex key
Expected Installation Time
30 minutes
WARNING:
Do not open actuator.
CAUTION:
Do not turn the 3 mm hex key against the
direction of the arrow.
Mounting Positions
Figure 2. Acceptable NEMA 2-Positions.
Figure 3. Only Acceptable Position for NEMA Type 3R
Rating Using ASK75.1U Weather Shield.
The GCA actuator is UL listed to meet NEMA Type 3R
requirements (a degree of protection against rain, sleet,
and damage from external ice formation) when installed
with the Weather Shield (product number ASK75.1U) and
outdoor-rated conduit fittings. Actuator must be in the
vertical position.
Prerequisites
NOTE: Actuator is shipped from the factory with 5°
preload. When power is applied to the actuator,
the preload is released. To manually release the
preload, insert the 3 mm hex key in the override
opening and turn the key in the direction of the
arrow. See Manual Override.