Technical data
Power supply GDB1..9E
Operating voltage (SELV/PELV) / Frequency AC 24 V ~ ±20 % (19,2…28,8 V ~) / 50/60 Hz
DC 24…48 V ±20 % (19,2…57,6 V )
1)
Power consumption running GDB141.9E
GDB161.9E
2 VA / 1 W
2.1 VA / 1.2 W
Power consumption holding GDB141.9E
GDB161.9E
0.5 W
0.7 W
Power supply GDB341.9E
Operating voltage / Frequency AC 100…240 V ~ ±10 % (90…264 V ~) / 50/60 Hz
Power consumption running 5 VA / 1.6 W
Power consumption holding 0.9 W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
5 Nm
10 Nm
5 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ±
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
Inputs
Positioning signal for GDB141.9E
Operating voltage
AC 24 V ~ / DC 24…48 V
(wires 1-6/G-Y1)
(wires 1-7/G-Y2)
clockwise
counterclockwise
Positioning signal for GDB341.9E
Operating voltage
AC 100…240 V ~
(wires 4-6/N-Y1)
(wires 4-7/N-Y2)
clockwise
counterclockwise
Positioning signal for GDB161.9E
Input voltage
Current consumption
Input resistance
(wires 8-2/Y-G0)
DC 0/2…10 V
0.1 mA
>100 kς
Max. permissible input voltage
Protected against faulty wiring
Hysteresis
DC 35 V limited to DC 10 V
max. AC 24 V ~ / DC 24…48 V
60 mV
Outputs
Position indicator (GDB161.9E)
Output signal
Output voltage U
Max. output current
(wires 9-2/U-G0)
DC 0...10 V
DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V