Connection cables
Cable length 0.9 m
Cross section of prewired connection cables 0.75 mm
2
Permissible length for signal lines 300 m
Degree of protection
Insulation class
AC 24 V ~ / DC 24…48 V , feedback potentiometer
AC 100…240 V ~, auxiliary switches
As per EN 60730
III
II
Housing protection IP 54 as per EN 60529
Environmental conditions
Operation
Climatic conditions
Mounting location
Temperature extended
Humidity (non-condensing)
IEC 60721-3-3
Class 3K5
interior, weather-protected
-32…+55 °C
<95 % r.F.
Transport
Climatic conditions
Temperature extended
Humidity (non-condensing)
IEC 60721-3-2
Class 3K5 / Class 2K3
-32…+70 °C
<95 % r.F.
Storage
Climatic conditions
Temperature extended
Humidity (non-condensing)
IEC 60721-3-1
Class 1K3
-32…+50 °C
<95 % r.F.
Mechanical conditions Class 2M2
Standards, directives and approvals
Product standard
EN 60730
Part 2-14 / Particular requirements for electric
actuators
Electromagnetic compatibility
(Applications)
For use in residential, commercial, light-industrial
and industrial environments
EU Conformity (CE) A5W00003842
2)
RCM Conformity A5W00003843
2)
EAC Conformity Eurasian conformity
UL UL as per UL 60730 http://ul.com/database
cUL as per CSA-C22.2 No. 24-93
Environmental compatibility
The product environmental declaration A5W00026068
2)
contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D see „Dimensions“, p. 9
Weight
Without packaging 0.69 kg
1)
cUL: Permitted only to DC 30 V
2)