Data Sheet for Product

Table Of Contents
Technical Instructions OpenAir GEB Non-Spring Return, 24 Vac,132 lb-in, Rotary Electronic Damper Actuators
Document Number 155-318P25
May 19, 2014
Page 10 Siemens Industry, Inc.
Control Signal
Adjustment,
Continued
Uo = 2; U = 16V
Umin = minimum control signal
Umax = maximum control signal
Figure 14. Example.
Dual auxiliary switch
GEB164.1U,
GEB136.1U
Actuator scale: Clockwise
Adjustment range for switches A and B:
Setting interval: 5°
Switching hysteresis: 2°
Actuator Scale: counterclockwise
To change the settings of A and B:
NOTE: The scale is only valid when the
actuator is in the "0" position on
clockwise motion.
Use the adjustment tool provided
with the actuator to turn the
switch adjustment dials to the
desired signal setting.
Factory setting:
Switch A
Switch B 85°
Figure 15. Dual Auxiliary Switch Dials.
.
NOTE: Use the long arm of the "" to point to the position of switch A. Use the
narrower tab on the red ring to point to the position of switch B.
DIP Switch
Functionality
GEB161
GEB164
Description Label Description Function
Counterclockwise
Clockwise Rotary angle direction
Active
0 Off
Self-adaptation to
mechanical range
2-10 Vdc 2-10
0-10 0…10 Vdc
GEB161: Positioning
control signal
2-10 or 0-10
Offset 0-5V
Span 2-30V
ADJ 0-10 0...10 Vdc
GEB164: Positioning
signal. Turn on or off
capability to adjust
offset/span.
Figure 16. DIP Switches.